Series S36 Instruction Manual
Chapter 7 Troubleshooting and Repair
800120
7-7
Analog Output Calibration
To check the 4
–
20 mA circuit, connect a DVM in series with the output loop. Select
zero or full scale (from the second level of the hidden Diagnostics menu) and then
actuate the
ENTER
key. This action will cause the meter to output its 4 mA or 20 mA
condition. If the DVM indicates a current greater than ± 0.006 mA from 4 or 20 mA,
adjust the setting up or down until the output is calibrated.
Note: these settings are not for adjusting the output zero and span to match a flow
range, that function is located in the Output Menu.