Series S36 Instruction Manual
Chapter 3 Operation
3-8
800120
Alarms Menu
Password
ENTER
Use
keys to access menus
Alarms
Menu
Relay Alarm 1
More >
ENTER
Run Mode
Relay Alarm 2
More >
Alarm LOG
xx Files (ENTER)
Clear Alarm LOG?
YES or NO
<Measure> units
xxxx
xxxx
Alarm File
Time
Date
(Press EXIT to return
to Alarm LOG)
<Measure>
None
Mass
Volume
Temp 1,2
Density
* Energy
<Measure>
None
Mass
Volume
Temp 1,2
Density
* Energy
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Mode>
None
HIGH Alarm (>)
LOW Alarm (<)
<Measure> units
-+
*
Energy EM Meters Only
Example for Setting an Alarm
The following shows how to set Relay Alarm 1 to activate if the mass flow rate is greater than 100 lb/hr. You can
check the alarm configuration in the Run Mode by pressing the
keys until Alarm [1] appears. The lower line
displays the mass flow rate at which the alarm activates. Note: all outputs are disabled while using the Setup
Menus.
First, set the desired units of measurement:
1.
Use
keys to move to the Units Menu (see page 3-13).
2.
Press
key until Mass Flow Unit appears. Press
ENTER
.
3.
Press
key until lb appears in the numerator. Press
key to move the underline cursor to the
denominator. Press the
key until hr appears in the denominator. Press
ENTER
to select.
4.
Press
key until Units Menu appears.
Second, set the alarm:
1.
Use
keys to move to the Alarms Menu.
2.
Press the
key until Relay Alarm 1 appears.
3.
Press
key to access Measure selections. Press
ENTER
and use the
key to select Mass. Press
ENTER
.
4.
Press
key to select the alarm Mode. Press
ENTER
and use
key to select HIGH Alarm. Press
ENTER
.
5.
Press
key to select the value that must be exceeded before the alarm activates. Press
ENTER
and use the
keypad to set 100 or 100.0. Press
ENTER
.
6.
Press the
EXIT
key and then
ENTER
to save changes and return to the Run Mode screen. (Alarm changes
are always permanently saved.)
Содержание SonoPro S36 Series
Страница 44: ...Series S36 Instruction Manual Chapter 3 Operation 3 5 800120 Output Menu...
Страница 78: ...Series S36 Instruction Manual Chapter 7 Troubleshooting and Repair 800120 7 2 Hidden Diagnostics Menus...
Страница 92: ...Series S36 Instruction Manual Appendix A Specifications A 2 800120...
Страница 96: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 2 800120 Pipe Chart...
Страница 97: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 3 800120...
Страница 98: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 4 800120...
Страница 99: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 5 800120...
Страница 100: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 6 800120...
Страница 101: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 7 800120...
Страница 102: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 8 800120...