D.  RECEIVING AND INSTALLING REMOTE CONDENSING 

UNITS

NOTE

The remote condensing units may be sent prior to 

delivery of the freezer.
The freezer requires one remote condensing unit 

per cylinder.
Remote condensers for 60Hz units are shipped 

from the factory charged with 20 lbs of refrigerant. 

Remote condensers for 50Hz units are shipped 

without refrigerant and require 20 lbs of refrigerant.

1. 

Upon arrival, check the entire remote condenser 

units for any damage that may have occurred 

during transit. With the method of packaging used, 

the remote condensers should arrive in excellent 

condition. The carrier is responsible for all damage 

in transit, whether visible or concealed. Do not pay 

the freight bill until the remote condenser units have 

been checked for damage. Have the carrier note 

any visible damage on the freight bill. If concealed 

damage or a shortage is found later, advise the carrier 

within 10 days and request inspection. The customer 

must place a claim for damages and/or shortages 

in shipment with the carrier. Stoelting cannot make 

any claims against the carrier.

2. 

Remove cardboard covering off the condensing 

units.

3. 

Place the condensing units in their predetermined 

location, either on the roof or on the ground. A 

crane or forklift is needed if the units are placed on 

a roof. The condensing units weigh approximately 

200 lbs. each.

4. 

Using ratchet with a 1/2” socket, remove the two lag 

bolts that secure the condensing unit to the pallet.

5. 

Place the condensing units on 4” x 4” treated 

wood or similar material so that the units are not 

sitting directly on the ground or the roof. Secure 

the condensing units to the 4” x 4” using lag bolts. 

Adhere to all local, state, and federal codes governing 

this type of installation. Some areas have specific 

“hurricane-proof” requirements for roof installations. 

Allow at least 3 feet of clearance on the air intake 

and discharge sides of the condensers. Do not set 

the condensers so that one is blowing air directly 

into the other condensing unit. The ideal set up is to 

have all the condensing units set in a row (Fig. 2-1).

6. 

Connect the refrigeration lines to the condensing 

unit:
For condensing units without piercing unions
a.  Braze the suction line and liquid line from the line 

sets to the condensing unit. When brazing, wrap 

the shut off valve with a cold wet rag and make 

sure that the valve is fully open. If the valve is not 

wrapped, damage may result. When installing the 

suction line, angle it towards the condensing unit 

so that oil can flow back towards the compressor.

b.  Use good piping practices. Keep pipes as clean as 

possible. Do not let any debris or copper shavings 

get inside system otherwise the refrigeration 

valves may not work properly.

For condensing units with piercing unions
a.  Thread the line set fittings onto the condensing 

unit by hand.

b.  Tighten the fittings with a wrench until the 

coupling bodies “bottom out”.

c.  Use a torque wrench to tighten the fittings to 

46±1 ft-lbs.

NOTE

The piercing unions are a one-time connection. Do 

not loosen the fittings after installing or refrigeration 

charge will be lost.

Figure 2-1 Remote Condenser Installation

(Top View)

Содержание Stoelting M202

Страница 1: ...Model M202B OPERATORS MANUAL Manual No 513666 Rev 6 A VOLLRATH DIVISION...

Страница 2: ......

Страница 3: ...ice and without incurring any obligation to modify or provide new parts for machines built prior to date of change DO NOT ATTEMPT to operate the machine until instructions and safety precautions in th...

Страница 4: ...ts with the correct part number or an equivalent part We strongly recommend that you do not use replacement parts of inferior quality Safety Alert Symbol This symbol Indicates danger warning or cautio...

Страница 5: ...3 3 Sanitizing 11 3 4 Freeze Down And Operation 11 3 5 Hold Cycle 12 3 6 Production From Hold 13 3 7 Italian Ice Freeze Down And Operation 13 3 8 Removing Mix From Machine 14 3 9 Cleaning The Machine...

Страница 6: ......

Страница 7: ...hnology Thismanual is designed to assist qualified service personnel and op erators in the installation operation and maintenance of the M202 frozen custard machine NOTE Product breakdown could happen...

Страница 8: ...rged and require 20 lbs of refrigerant Water cooled units are self contained and require a Standard Hose Adapter water fitting and a 1 2 OD drain fitting for each barrel Hopper Volume Two 5 4 gallon 2...

Страница 9: ...e safety precautions and operating instructions in this manual are read completely and are thoroughly understood Take notice of all warning labels on the machine The la bels have been put there to hel...

Страница 10: ...ing unit until the refrigeration lines have been connected the machine must have power for refrigerant charging Label the circuit breakers with information regarding which cylinder and condensing unit...

Страница 11: ...nsing unit to the pallet 5 Place the condensing units on 4 x 4 treated wood or similar material so that the units are not sitting directly on the ground or the roof Secure the condensing units to the...

Страница 12: ...tdamagetothesolenoid Also be aware of the electrical conduit inside custard machine while soldering the refrigeration lines d A liquid line dryer is supplied with the machine and should be the last co...

Страница 13: ...ve counterclockwise to decrease the pressure or clockwise to increase the pressure Turn the valve 1 4 turn at a time and wait at least 1 minute before makinganotheradjustment Connectagaugetothe suctio...

Страница 14: ...Owner s Manual 513666 8 M202B Model Machines...

Страница 15: ...isconnected G Donotoperateunderunsafeoperatingconditions Neveroperatethemachineifunusualorexcessive noise or vibration occurs 3 2 OPERATING CONTROLS AND INDICATORS Before operating the machine it is r...

Страница 16: ...otate and hopper refrigeration stops F Mix Low Light Indicator TheMIXLOWmessageappearsontheLCDdisplay to alert the operator of a low mix condition The messagedisplayswhenthereisapproximatelyone gallon...

Страница 17: ...arm Fig 3 3 C Make sure the flow control valve is shut by turning the control knob counterclockwise to the OFF position D Place a bucket under the slide E Pour the sanitizer into the hopper NOTE A sm...

Страница 18: ...product NOTE Adjustments take up to 1 minute before a noticeable difference is seen in the product NOTE A high pitched noise from the freezing cylinder is an indication that there is not enough mix en...

Страница 19: ...isplay reads ITALIAN ICE READY the freezing cylinder is at the correct temperature J Open the front gate D After the timer expires and all usable product is removed close the gate E Remove the slides...

Страница 20: ...e width of the opening 3 8 REMOVING MIX FROM MACHINE To remove the mix from the machine refer to the follow ing steps Make sure the gate on the faceplate is open NOTE The following instructions are fo...

Страница 21: ...move the slide from the faceplate and remove the faceplate D Remove the front wear bushing F Remove the auger assembly from the machine Pull the auger out of the freezing cylinder slowly using the sha...

Страница 22: ...t onto the auger shaft Do not lubricate the rear gasket B Lubricate the hex end of the auger shaft with a small amount of Total Blend lubricant C Install the springs and blades onto the first two posi...

Страница 23: ...w the air in the opposite direction of the normal airflow C SEMI ANNUALLY Replace Barrel Parts According To Schedule Follow the Parts Replacement Schedule below to keep the freezer operating properly...

Страница 24: ...inlet fitting The fitting is located at the rear of the machine Run the compressor for 2 3 minutes to open the water valve the front door must be attached for the compressor to run Blow out all the wa...

Страница 25: ...error could happen if the cutout value is not attained during Standby Mode or if the Ready signal does not come on in Custard Mode or Italian Ice Mode This error is generally caused by very low mix le...

Страница 26: ...enser If the control panel displays an E9 on an air cooled machine check for proper air clearance around the condenser In a water cooled machine check that the water is not shut off If the error persi...

Страница 27: ...m for that barrel set too warm for the mix 2 Call Stoelting White Glove Service 3 Condenser on remote unit is blocked 3 Check for blockage and clean if necessary 4 Water cooled machine has water shut...

Страница 28: ...Owner s Manual 513666 20 M202B Model Machines...

Страница 29: ...46 Decal Caution Hazardous Moving Parts 324509 Decal Cleaning Instructions 324548 Decal Adequate Ventilation 6 324566 Decal Wired According To 324594 Decal Attention Heat Sensitive 2 324686 Decal Dang...

Страница 30: ...000 50 Spring 10 per barrel C 2000 51 Blade 9 per barrel NT 0010 Wing Nut Stainless Steel 1 per barrel SL 0010 Seal Beater Shaft 1 per barrel 149014 Bushing Front Auger Support 1 per barrel 336588 Fac...

Страница 31: ...00 19 Slide Long Chute 1 C 4000 20 Slide Short Chute 1 754141 Tube Flow Control Hopper 1 per barrel 2202565 Tray Drain 1 2202588 Cover w Handle Hopper 1 per barrel 2205963 Flow Control Rod 1 per barre...

Страница 32: ...Owner s Manual 513666 24 M202B Model Machines...

Отзывы: