7.3 CHECKING THE CO

2

 AND ADJUSTING THE 

GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE 
AID OF A PROPERLY CALIBRATED FLUE GAS ANALYSER.
Isolate the appliance from the electrical supply and remove 

the appliance casing as described in 4.7.1. Set the lue gas 

analyser to read CO2 and insert the probe into the lue analysis 

test point (Y1-Z1 ig. 40). Restore the electrical supply to the 

boiler and switch the boiler to the OFF mode.
Have access to the printed circuit board, locate and open the 
closing plug on the dash board (L2), locate and press the CO 

button (see ig. 43 pos. SW1). Press the button the number of 

times according the function requirement as per 7.3.1.

7.1 CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, 
the relevant commissioning procedure must be undertaken to 
ensure the continued safe operation of the appliance. Particular 
attention should be made to ensure gas tightness, water tight-
ness and the electrical integrity of the appliance.

7.2 APPLIANCE MODES OF OPERATION

NOTE

There must be suficient 

system water pressure (min. 0.5 bar) 

to ensure the water pressure switch is activated. If there is in-

suficient system pressure the pump and fan will be prevented 

from operating and the low-pressure fault code will be indicated.

7.2.1 SELECTOR SWITCH IN THE OFF/RESET POSITION

When the selector switch is in the OFF/RESET position, the 
following functions are active.

Active functions

:

• 

frost-protection system

• 

pump & actuator anti-block.

7.2.2 ON-BOARD FUNCTIONS

• 

CO FUNCTION:

 the CO function when activated, will allow the 

appliance to run at CH maximum, DHW maximum or minimum 
output whilst a combustion analysis check or a mechanical gas 
valve calibration is being carried out. Whilst the CO function 
is active, all other functions are disabled (minimum power 
operating period, anti-cycle, set-point, etc). Once enabled, 
the CO function will remain active for a 15-minute period, or 
until the function is manually deactivated 

• 

FROST-PROTECTION: 

this function is only active when 

there are no requests for heating or HW. If the temperature 
drops below 5°C, the boiler will operate on minimum power 
until the temperature of the thermistors reaches 35°C for CH 
and 55°C for DHW. Thereafter the pump & fan will over-run 
for 30-seconds.

• 

ANTI-CYCLE FUNCTION:

 the anti-cycle function ensures the 

burner remains switched off for at least 3-minutes after the 
set-point hysterisis (set-point + 5-deg) for CH heat request.  

• 

PUMP ANTI-BLOCK FUNCTION: 

when there has been no 

heating or HW request for 24-hours, the anti-block cycle is 
activated. The pump will be activated for a period of 30-sec-
onds.

• 

ACTUATOR ANTI-BLOCK FUNCTION: 

when there has been 

no heating or HW request for 24-hours, the anti-block cycle 

is activated. The divertor valve actuator will motor briely to 

the heating position, and then back to the DHW position. The 

pump will run briely.

• 

SARA function:

 the SARA function permits the boiler (when 

the set-point is within the SARA range) to automatically adjust 

(raise) the heating low outlet temperature should the room 

thermostat contacts remain closed for more that 20-minutes.

• 

DHW PRE-HEAT FUNCTION:

 when the DHW pre-heat func-

tion is enabled, the appliance will light periodically to maintain 
the temperature of the DHW heat exchanger. When the 
DHW thermistor and the primary thermistor fall below 35°C 

and 55°C respectively, the boiler will ire on m25% 

power until the primary thermistor exceeds 55°C. Thereafter 
the pump will over-run for a period of 30-seconds.

7.2.3 HEATING MODE

With the selector switch in the heating  & hot water position 
and any additional controls (time clock, programmer, room 
thermostat, etc.) calling for heat, the appliance will operate 
in the heating mode. The pump and fan will be activated via 

the low temperature sensor. When the fan is sensed to be 

operating correctly (tacho signal), the ignition sequence com-
mences. Ignition is sensed by the electronic circuit to ensure 

lame stability at the burner. Once successful ignition has been 

achieved, the electronic circuitry increases the gas rate to 75% 
for a period of 15 minutes.
The speed of the fan and therefore the output of the boiler is 
determined by the temperature of the water sensed by the 

low temperature sensor, consequently a high temperature at 

the low sensor results in a lower fan speed. As the water tem

-

perature increases, the temperature sensors – located on the 

low pipe of the boiler – reduce the fan speed via the electronic 

circuitry. Depending on the load, either the water temperature 
will continue to rise until the set point is achieved or the water 

temperature will fall whereby fan speed will increase relative to 
the output required. When the boiler has reached the set point 
(+ hysterisis), the burner will switch off. The built-in anti-cycle 
device prevents the burner from re-lighting for approximately 

3-minutes. When the temperature of the low sensor falls below 

the set point (- hysterisis), the burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the appli-
ance will re-attempt ignition a further 4-times then go to lockout. 
When the set-point has been reached (the position of the heating 
temperature selector) as measured at the primary thermistor, the 
appliance will begin the modulation phase whereby the fan and 
gas valve will continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-point 
by 5°C (hysterisis), the burner will shut down. A new ignition 
sequence will be enabled when the 3- minute anti-cycle has 
been performed and the temperature at the primary thermistor 
has dropped 5°C (hysterisis) below the set-point.

7.2.4 DHW MODE

With the selector switch in either the hot water only or heating 
& hot water position, the appliance will operate in the hot water 

mode whenever a DHW outlet is opened. A low rate exceeding 

2-litres per minute will activate the DHW low switch whereupon 

the pump and fan will be activated via the low temperature 

sensor. When the fan is sensed to be operating correctly (tacho 
signal), the ignition sequence commences. Ignition is sensed 

by the electronic circuitry to ensure lame stability at the burner. 

Once successful ignition has been achieved, the electronic 
circuit allows the gas rate to achieve the modulation value.

NOTE

When the request for heating and/or hot water has been satis-

ied, the appliance pump and fan may continue to circulate to 

dissipate any residual heat within the appliance.

ATTENTION

Gas type and appliance output 

must be set 

according to the 

speciic appliance speciication. Vokèra accepts no responsi

-

bility if the gas type is not correctly adjusted according to the 

respective appliance speciication as detailed on the appliance 

data badge.

SECTION 7 - CHECKS, ADJUSTMENTS AND FAULT FINDING

L2

Fig. 43

SW1

use the supplied 

screwdriver to push the 

CO botton (SW1)

Содержание Vision C

Страница 1: ...ctions THESE INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems...

Страница 2: ...3A 4 Flue system 13 3A 5 Air supply 14 3A 6 Water circulation 14 3A 7 Electrical supply 14 3A 8 Mounting on a combustible surface 14 3A 9 Timber framed buildings 14 3A 10 Inhibitors 14 3A 11 Showers 1...

Страница 3: ...tically Dear Customer Your Vok ra Vision boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and ef...

Страница 4: ...shows the temperature values Pressure gauge shows the current pressure of your heating system the gauge should be set between 1 and 1 5 BAR When the appliance is oper ating the gauge may rise or fall...

Страница 5: ...ADVANCE ON fun ction is active Displayed when the ADVANCE OFF fun ction is active Displays current minutes past the hour Displays current hour of the day 24 hour clock in 30 minute segments lar ge se...

Страница 6: ...y of week setting procedure NOTE the time of day is shown on the display and is also indicated on the 24 segmented display as a lashing segment 1 4 CHANGING THE HEATING PATTERN The built in clock is p...

Страница 7: ...he programmed heating pattern AUTO ON Heating is in an ON period according to the programmed heating pattern MAN OFF Heating is being controlled manually and is switched constantly OFF MAN ON Heating...

Страница 8: ...ow a period of at least two minutes before re setting the appliance 2 6 EXPLANATION OF FEATURES Although the Vok ra Vision has been designed for simplicity of use it utilises the latest in boiler tech...

Страница 9: ...r A01 Ignition failure lame not sensed internal fault Final Reset check appliance operation A02 Limit thermostat fault Final Reset check appliance operation A03 Fan tacho signal fault Final Reset chec...

Страница 10: ...on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet is handed to the person responsible for the property in which the applianc...

Страница 11: ...nd the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisied the appliance pump and fan may continue to operate to dissipate any residual heat within th...

Страница 12: ...mum system volume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Vision 25C Vision 30C Height mm 715 Width mm 405 Depth mm 248 Dry weight kg 27 28 2 6 Clearances Vision 25C Vision 30C Sides 12mm T...

Страница 13: ...to the roof lashing As determined by the ixed collar of the vertical terminal R To the side of a boundary 300 mm S To the side of an opening or window on a pitched roof 600 mm T Below an opening or w...

Страница 14: ...ansion vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is suficient however if the system...

Страница 15: ...itted on a wall of combustible mate rial there is no requirement for a sheet of ireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be itted in a timber framed bu...

Страница 16: ...An alternative method of illing the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above...

Страница 17: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum lue length for each bend 45 bend 1 3 me...

Страница 18: ...REAR FLUE ig 15 rear lue outlet only Using the template provided mark and drill a 125mm hole for the passage of the lue pipe The hole should be drilled LEVEL to ensure any condense luid that forms is...

Страница 19: ...ired number of lue extensions or bends up to the maximum equivalent lue length between the boiler and vertical lue assembly see ig 14 Ensure that any horizontal sections of the lue system have a minim...

Страница 20: ...e kit for termination The horizontal terminal is supplied with a built in converter box and cannot be shortened A 130mm hole is required for the passage of the concentric terminal through the wall The...

Страница 21: ...ad can be used for connection to the electrical supply Connect the ly lead to a fused plug or fused isolator in the following way brown wire to LIVE supply blue wire to NEUTRAL supply green yellow to...

Страница 22: ...ectrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move the selector switch to the ON position the appliance will now...

Страница 23: ...LY AND IS PROPERLY SECURED ENSURE ALL PIPE WORK IS RE CHECKED FOR TIGHT NESS RE FIT APPLIANCE CASING COMPLETE BENCHMARK CHECKLIST FOR UK ONLY Complete details of the boiler controls installation and c...

Страница 24: ...n the reverse order 6 7 LOWER AUTOMATIC AIR RELEASE VALVE ig 28 Carry out component removal procedure as described in 6 4 Remove the expansion pipe locking pin B from the pump as sembly and remove the...

Страница 25: ...dition taking care to Fig 34 6 13 ELECTRODES ig 34 Carry out component removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from...

Страница 26: ...removal procedure as described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW...

Страница 27: ...unscrew the inlet connection Unscrew the nut E2 Lift the DHW low switch housing from its seating If necessary remove the locking pin F2 from the DHW low switch taking care not to lose the loat contain...

Страница 28: ...ow 35 C and 55 C respectively the boiler will ire on minimum 25 power until the primary thermistor exceeds 55 C Thereafter the pump will over run for a period of 30 seconds 7 2 3 HEATING MODE With the...

Страница 29: ...emed as immediately dangerous 7 5 CHECKING THE EXPANSION VESSEL Carry out the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a sui...

Страница 30: ...mpletion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultinding the elect...

Страница 31: ...ressed in hundreds e g 25 2 500 rpm GAS VALVE CALIBRATION Connect the boiler to the power supply Open the gas tap Set the function selector to OFF RESET monitor off Remove the screws E remove the casi...

Страница 32: ...st the temperature of the heating system indirectly by changing the required room temperature from between 15 C 25 C this will allow the PCB to recalculate the system temperature required the default...

Страница 33: ...controls manufacturer and or Vok ra technical department should you require more speciic information on the suitability of a particular control Further guidance on the recom mended practice for the in...

Страница 34: ...ssure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermistor NTC brown CN3 blue F Hv 1 2 7 1 C...

Страница 35: ...HE APPLIANCE GAS TYPE To convert the appliance to another gas type it is necessary to change the injector and adjust the gas valve CO2 To change the injector see 6 12 1 Toreplacethelangeonthesilencer...

Страница 36: ...7 3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw ig 44 using a suit able screwdriver remove the protection plug usi...

Страница 37: ......

Страница 38: ...36...

Страница 39: ...38...

Страница 40: ...ies vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve t...

Отзывы: