6
3.6.1
PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered
capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular
to avoid the possibility of freezing. Particular
attention should be paid to pipes passing through
ventilated areas such as under floors, loft space
and void areas.
3.6.2
AUTOMATIC BY-PASS
The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling’.
3.6.3
DRAIN COCKS
These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance. The drain cocks
must be manufactured in accordance with BS
2879.
3.6.4
AIR RELEASE POINTS
These must be positioned at the highest points
in the system where air is likely to be trapped.
They should be used to expel trapped air and
allow complete filling of the system.
3.6.5
EXPANSION VESSEL
The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to
10 litres of expansion from within the system,
generally this is sufficient, however if the system
has an unusually high water content, it may be
necessary to provide additional expansion
capacity.
3.6.6
FILLING POINT
A method for initial filling of the system and
replacing water lost during servicing etc. is
required (see fig. 14). This method of filling must
comply with the current Water Supply (Water
Fittings) Regulations 1999 and Water Bylaws
2000 (Scotland).
3.6.7
LOW PRESSURE SEALED SYSTEM
An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (see fig. 5). The cold feed from
the make-up vessel or tank must be fitted with
an approved non-return valve and stopcock for
isolation purposes. The feed pipe should be
connected to the return pipe as close to the boiler
as possible.
3.6.8
FREQUENT FILLING
Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during
the installation of the appliance to ensure all
aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3.7
ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V
@ 50Hz electrical supply; it must be protected
with a 3-amp fuse. The method of connection to
the mains electricity supply must allow for
complete isolation from the supply. The preferred
method is by using a double-pole switch with a
contact separation of at least 3mm. The switch
must only supply the appliance and its
corresponding controls, i.e. time clock, room
thermostat, etc. Alternatively an un-switched
shuttered socket with a fused 3-pin plug both
complying with BS 1363 is acceptable.
3.8
MOUNTING ON A COMBUSTIBLE SURFACE
If the appliance is to be fitted on a wall of
combustible material, a sheet of fireproof material
must protect the wall.
3.9
TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed
building, it should be fitted in accordance with
the Institute of Gas Engineers publication (IGE/
UP/7) ‘Guide for Gas Installations in Timber
Frame Buildings’.
3.10
INHIBITORS
Vokera recommend that a inhibitor - suitable for
use with low water-content, copper heat
exchangers - is used to protect the boiler and
system from the effects of corrosion and/or
electrolytic action. The inhibitor must be
administered in strict accordance with the
manufacturers* instructions.
*Fernox and Sentinel manufacture products that
have proved suitable for use with Vokera
appliances. Vokera Ltd. cannot comment on the
suitability of any other such product with our
appliances.
Fig. 5
Make-up vessel
or tank
Automatic
air-vent
Non-return
valve
Stopcock
5.0 metres minimum
Heating return