43
•
Without DHW
Installation is simple, requiring no additional elements. The ambient temperature probe located at
the back of the boiler can be extended into the interior of the house. Using the chrono function and
this probe inside the room and activating the ECO mode, the boiler will work for the programmed
period, turning off whenever the room temperature is reached and turning it on again when it drops
by 1ºC.
Figure 15- Installation scheme without DHW
To change the installation configuration, access the technical menu
TPAR > PASSWORD > TP08
and
change the parameters:
P77=0
- Deactivate DHW sensor
P26=5
- Define installation type (without DHW)
P75=4/0
–
Enable/disable wired remote thermostat
–
In this case the remote thermostat overrides
the controller’s programmed time
1 - Controller
4 - PIKO thermostat
5 - AQS Deposit
6 - Supply network
7 - Thermostatic mixing valve
–
Anti-condensation
11 - 2Ways Thermostat