VIP Vision Access Control Installation Guide - Version: VIPACC-Q219.1
14
2.3 Installation
2.3.1 Setting Up Door Lock Jumpers (2P42 and 2P81 ONLY)
There are 8 relays and 8 jumpers for on the main board. The jumpers must be configured for proper NO (Normally
Opened) / NC (Normally Closed) output. Default setting is pin 1-2 shorted, i.e. NO output - Power is supplied to the lock
only when it is being unlocked. If you need NC output, please short pin 2-3.
2.3.2 Connecting Door Locks
a) Fail Secure type door lock connection - Supply power to unlock.
Typical Fail Secure type door lock: Electric strikes, drop bolts (fail secured type).
b) Fail Safe type door lock connection - Remove power to unlock.
Typical Fail Secure type door lock: Electromagnetic locks, drop bolts (fail
safe type).
It is strongly recommended to use separate power supply for door locks if more than 4 locks are installed.
Port No.
2P42
2P81
JK5
Lock/Unlock control of door 1
Lock/Unlock control of door 1
J35
JK6
Lock/Unlock control of door 2
Lock/Unlock control of door 2
J37
JK7
Lock/Unlock control of door 3
Lock/Unlock control of door 3
JK39
JK8
Lock/Unlock control of door 4
Lock/Unlock control of door 4
J41
JK9
Internal Alarm Output 1
Lock/Unlock control of door 5
J18
JK10
Internal Alarm Output 2
Lock/Unlock control of door 6
J22
JK11
Internal Alarm Output 3
Lock/Unlock control of door 7
J20
JK12
Internal Alarm Output 4
Lock/Unlock control of door 8
J24