3.3 Advanced Functions (continued)
3.3.6 Door Open Timeout
The VIP Vision access controller is able to notify the operator when a door is opened for a duration exceeding the preset
period. You must first add the door sensor (reed switch) to feed back the status of the door to the access control.
1. Click the Console icon.
2.
Choose the door to be configured by right clicking the door name and clicking Door Configuration.
3. Following the image below, turn on the Door, Alarm and Door Sensor switches, set a Close Timeout time (example:
10 seconds) and select the Overtime check box.
4. Click “OK” to save.
5.
Click the Alarm button, then select the door being configured and click Door Unclosed Alarm.
6.
Switch on “Door Unclosed Alarm” and “Alarm Sound”. Click “Save” to finish.
When finished, the PC speak will sound if the door is opened for a period longer than the preset period. Note:
1) Smart PSS must be installed and running on a PC when the notification is required.
2) PC must equipped with a speaker.
3) The notification is a continue short and quick beep sound for about 1 second only.