Start-up
87
Steps
(continued)
3. Integrate the control unit in the LON BUS system
Single-boiler system only
The LON communication module
(accessory) must be inserted
(see page 111).
Set the LON participant number
Set the LON participant number via
coding address ”77” in coding 1
(factory setting: ”77: 1”).
See page 115 for coding 1.
Please note:
The same number must
not
be
assigned twice within a LON BUS
system.
Update the LON participant list
This is only possible when all participants are connected and the control unit is
coded as the error manager (coding ”79: 1”).
1.
Press
w
and
simultaneously for
approx. 2 seconds.
2.
Press
D
.
The participant check is initiated
(see also page 88).
The participant list is updated after
approx. 2 minutes.
The participant check is terminated.
Example of single-boiler system with Vitotronic 050 heating circuit controls and Vitocom connected downstream
Participant No. 1
Coding ”77: 1”
Participant No. 10
Coding ”77: 10”
Participant No. 11
Set coding ”77: 11”
Participant No. 100
Control unit is error
manager
Coding ”79: 1”
Control unit is not error
manager
Coding ”79: 0”
Control unit is not error
manager
Coding ”79: 0”
Unit is error manager
–––
Transmit time via LON
Set coding ”7b: 1”
Time is received via LON
Set coding ”81: 3”
Time is received via LON
–––
Transmit outdoor
temperature via LON
Set coding ”97: 2”
Outdoor temperature is
received via LON
Set coding ”97: 1”
–––
5
3
5
1
3
3
8
v
1
.8
1 2 3 4 5 6 7
Vitotronic 100
Vitotronic 050
Vitotronic 050
Vitocom
LON
LON
LON
Содержание Vitotronic 100 GC1
Страница 43: ...Installation 43 Overview of Electrical Connections VD2 VD2A CT3 only continued 5351 338 v1 8 29 20 A1 ...
Страница 44: ...Installation 44 Overview of Electrical Connections CM2 only continued 5351 338 v1 8 ...
Страница 128: ...Additional information 128 Wiring Diagrams continued Line voltage motherboard 5351 338 v1 8 A11 A3 floating ON ON ...
Страница 131: ...Additional information 131 Parts List 5351 338 v1 8 ...