Heating system types
26
Circuit Diagram 10
(continued)
Possible applications
For heating circuits with different
temperatures.
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
heating contractor to check that this
recommendation is complete and fully
functional. Three-phase equipment
must be connected via additional
power contactors.
The Vitocrossal 300 is operated with
constant boiler water temperature by
means of the boiler control unit.
Two-stage or modulating burners can
be controlled.
The Vitocrossal 300 has two return
connections. The heating circuits with
the higher return temperature are
connected to the return connection at
the top, those with the lower
temperatures to the return connection
at the bottom.
Please note:
At least 15% of the take-off from the
rated output must be connected to the
return connection at the bottom.
The boiler water temperature which is
established in the heating mode is
higher than the maximum heating
circuit supply temperature by an
adjustable difference.
Available system accessories
Flue gas temperature sensor
Coding of
system type
Change required
Automatic change
00: 1
–––
With DHW tank:
Coding is automatically changed to ”00: 2”
02: 1
Set coding ”02: 2” for operation with
modulating burner
–––
0C: 4
Set coding ”0C: 0”
–––
0d: 2
Set coding ”0d: 0”
–––
5
3
5
1
3
3
8
v
1
.8
IMPORTANT
Содержание Vitotronic 100 GC1
Страница 43: ...Installation 43 Overview of Electrical Connections VD2 VD2A CT3 only continued 5351 338 v1 8 29 20 A1 ...
Страница 44: ...Installation 44 Overview of Electrical Connections CM2 only continued 5351 338 v1 8 ...
Страница 128: ...Additional information 128 Wiring Diagrams continued Line voltage motherboard 5351 338 v1 8 A11 A3 floating ON ON ...
Страница 131: ...Additional information 131 Parts List 5351 338 v1 8 ...