Installation
70
Connection of Single Combustion Air Device on Multiple Boiler Systems
Connection of the combustion air
blower
A
Common Combustion Air Device
Interface
B
Combustion air device motor
120VAC, 5 FLA max.
C
Proving switch rated for 120 VAC
D
Power supply, 120 VAC
¨
Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
See blower manual for current
rating to correctly select the fuse.
See Common Combustion Air
Device Interface manual for
Installation and Operating details.
1. Disconnect power to control and
burner.
2. Make the connections as shown
in the diagram.
5
3
5
1
3
3
8
v
1
.8
D
Содержание Vitotronic 100 GC1
Страница 43: ...Installation 43 Overview of Electrical Connections VD2 VD2A CT3 only continued 5351 338 v1 8 29 20 A1 ...
Страница 44: ...Installation 44 Overview of Electrical Connections CM2 only continued 5351 338 v1 8 ...
Страница 128: ...Additional information 128 Wiring Diagrams continued Line voltage motherboard 5351 338 v1 8 A11 A3 floating ON ON ...
Страница 131: ...Additional information 131 Parts List 5351 338 v1 8 ...