Troubleshooting
101
Diagnosis
(continued)
Faults with fault display on the programming unit
(continued)
Fault
code in
display
Behaviour of system
Cause of fault
Action
30
Burner is switched on and off by
the adjustable high limit
Short circuit
Boiler temperature sensor
Check boiler temperature sensor (see
page 50)
38
Burner is switched on and off by
the adjustable high limit
Open circuit
Boiler temperature sensor
Check boiler temperature sensor (see
page 50)
50
DHW pump ON:
set-point boiler temperature =
set-point DHW tank temperature,
priority controls are cancelled
or
In conjunction with DHW heating:
Tank heating is switched on and off
by Tank temperature sensor 2
Short circuit
DHW tank temperature sensor 1
Check DHW tank temperature sensor
(see page 51)
51
In conjunction with DHW heating:
Tank heating is switched on and off
by Tank temperature sensor 1
Short circuit
DHW tank temperature sensor 2
Check DHW tank temperature sensor
(see page 51)
58
DHW pump ON:
set-point boiler temperature =
set-point DHW tank temperature,
priority controls are cancelled
or
In conjunction with DHW heating:
Tank heating is switched on and off
by Tank temperature sensor 2
Open circuit
DHW tank temperature sensor 1
Check DHW tank temperature sensor
(see page 51)
59
In conjunction with DHW heating:
Tank heating is switched on and off
by DHW tank temperature sensor 1
Open circuit
DHW tank temperature sensor 2
Check DHW tank temperature sensor
(see page 51)
60
No output reduction
Return control open
Boiler with maximum temperature
Short circuit
Temperature sensor
aJ
A
Check temperature sensor
(see page 52)
68
No output reduction
Return control open
Boiler with maximum temperature
Open circuit
Temperature sensor
aJ
A
Check temperature sensor
(see page 52)
70
Shunt pump ON continuously
Short circuit
Temperature sensor
aJ
B
Check temperature sensor
(see page 52)
70
In conjunction with DHW heating:
Mixing valve of primary circuit
closed, no domestic hot water
heating
Short circuit
Temperature sensor
aJ
B
Check temperature sensor
(see page 52)
78
Shunt pump ON continuously
Open circuit
Temperature sensor
aJ
B
Check temperature sensor
(see page 52)
78
In conjunction with DHW heating:
Mixing valve of primary circuit
closed, no domestic hot water
heating
Open circuit
Temperature sensor
aJ
B
Check temperature sensor
(see page 52)
5
3
5
1
3
3
8
v
1
.8
Содержание Vitotronic 100 GC1
Страница 43: ...Installation 43 Overview of Electrical Connections VD2 VD2A CT3 only continued 5351 338 v1 8 29 20 A1 ...
Страница 44: ...Installation 44 Overview of Electrical Connections CM2 only continued 5351 338 v1 8 ...
Страница 128: ...Additional information 128 Wiring Diagrams continued Line voltage motherboard 5351 338 v1 8 A11 A3 floating ON ON ...
Страница 131: ...Additional information 131 Parts List 5351 338 v1 8 ...