Additional information
116
Coding 1
(continued)
Codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:Value
Possible change
07: 1
Boiler
Boiler sequence number in multi-
boiler system (in conjunction with
coding address ”01”)
07: 2
to
07: 4
Boiler sequence number in multi-boiler
system (in conjunction with coding
address ”01”)
08:
*1
Burner
(mod.)
Max. output of burner in kW
08: 0
to
08: 99
Maximum output variable from
0 to 99 kW;
1 increment = 1 kW
09:
*1
Burner
(mod.)
Max. output of burner in kW
09: 0
bis
09:199
Maximum output variable from
0 to 19900 kW:
1 increment = 100 kW
0A:
*1
Burner
(mod.)
Basic output of burner in %
0A: 0
to
0A:100
Basic output in %
Basic output in kW
Max. output in kW
x100%
=
15: 10
*2
Burner
(mod.)
Operating time of actuating drive
15: 5
to
15:199
Operating time variable
from 5 to 199 seconds
40:125
General
Operating time of actuating drive,
boiler isolation valve, 3-port mixing
valve or mixing valve motor in
conjunction with return
temperature control 125 minutes
40: 5
to
40:199
Operating time adjustable
from 5 to 199
77: 1
General
LON participant number
77: 2
to
77: 99
LON participant number
selectable from 1 to 99
Please note:
Each number may be assigned once
only
.
*1
The factory setting is determined by the boiler coding card.
*2
This setting is matched to the Vitocrossal.
5
3
5
1
3
3
8
v
1
.8
Содержание Vitotronic 100 GC1
Страница 43: ...Installation 43 Overview of Electrical Connections VD2 VD2A CT3 only continued 5351 338 v1 8 29 20 A1 ...
Страница 44: ...Installation 44 Overview of Electrical Connections CM2 only continued 5351 338 v1 8 ...
Страница 128: ...Additional information 128 Wiring Diagrams continued Line voltage motherboard 5351 338 v1 8 A11 A3 floating ON ON ...
Страница 131: ...Additional information 131 Parts List 5351 338 v1 8 ...