6.4 Vitocell 100-W, type CVB and CVBB adjacent to the boiler – 300 and 400 l, white fin-
ish, made from steel with Ceraprotect enamel coating for dual mode DHW heating
■ Adjacent to the boiler
■ With internal indirect coil, made from steel, with Ceraprotect
enamel coating
■ For dual mode DHW heating
For further technical details, see the separate datasheet for the Vitocell 100-B.
Type
CVBB
CVB
Cylinder capacity
(AT: Actual water capacity)
l
300
400
Heating water capacity
l
16
17
Gross volume
l
316
417
DIN registration no.
9W242/11-13 MC/E
Connections
(male thread)
Heating water flow and return
R
1
1
DHW and cold water
R
1
1¼
DHW circulation
R
1
1
Permiss. operating pressure
Heating water, solar and DHW sides
bar
MPa
10
1
10
1
Permiss. temperatures
– Heating water side
°C
160
160
– Solar side
°C
160
160
– DHW side
°C
95
95
Standby heat loss
kWh/24 h
1.65
1.80
Dimensions
Length a (
7
)
mm
667
859
Width b
mm
744
923
Height d
mm
1734
1624
Weight
kg
166
167
Energy efficiency class
B
B
Separate DHW cylinders for Vitodens 200-W
(cont.)
58
VIESMANN
VITODENS
6
5853906
Содержание Vitodens 200-W B2HE
Страница 154: ...154 VIESMANN VITODENS...
Страница 155: ...VITODENS VIESMANN 155 5853906...