Flue terminal position
Horizontal flue systems
Position
Minimum spacing
mm
a
Directly below an window that can be opened,
air vent or any other ventilation opening
300
b
Below gutter drain or soil pipe
75
c
Below eaves
200
d
Below a balcony
200
e
From vertical drain or soil pipes
150
f
From internal and external corners
300
g
Above adjacent ground or balcony level/roof
300
h
From a surface facing the terminal
600
i
Facing terminals
1200
j
From opening door/window in carport into
dwelling
1200
k
Vertically from a terminal on same wall
1500
l
Horizontally from a terminal on same wall
300
m
Adjacent to opening
300
n
Below carport/roof
200
Installation Requirements
(cont.)
18
Preparing for installation
58
62
670
GB