Expansion vessel
The table shows the maximum system
volume that the integral expansion
vessel can sustain under different
charge pressure conditions. If the sys-
tem volume exceeds that shown, an
additional expansion vessel must be
fitted and connected to the heating
system primary return pipe as close
as possible to the appliance. If an
extra vessel is required, ensure that
the total capacity of both vessels is
adequate.
Further details are available in the
current issues of BS 5449 and BS
6798.
Note
If the pressure gauge rises by 1.5 bar
when the appliance is at maximum
temperature with all radiators in circu-
lation an extra expansion vessel is
required.
Vessel charge and initial system
pressure
bar
0.5
1.0
1.5
psi
7.3
14.5
21.5
Total water content of system
using 8 litre capacity expansion
vessel supplied with appliance
litres
106
75
42
gallons
23
16.5
9
For systems having larger capa-
city, multiply the total system ca-
pacity in litres by the factor to
obtain the total minimum expan-
sion vessel capacity required
0.0833
0.11
0.16
Installation Requirements
(cont.)
26
Preparing for installation
58
62
670
GB
Содержание Vitodens 100
Страница 41: ...Opening the control unit housing Electrical connections 41 Installation 5862 670 GB Installation ...
Страница 82: ...A1 Main PCB A2 Programming unit Connection and wiring diagrams combi boiler 82 Designs 5862 670 GB ...
Страница 84: ...A1 Main PCB A2 Programming unit Connection and wiring diagram system boiler 84 Designs 5862 670 GB ...
Страница 88: ...Parts lists cont 88 Parts lists 5862 670 GB ...
Страница 89: ...Parts lists cont 89 Parts lists 5862 670 GB Service ...
Страница 90: ...Parts lists cont 90 Parts lists 5862 670 GB ...
Страница 91: ...Parts lists cont 91 Parts lists 5862 670 GB Service ...
Страница 95: ...95 5862 670 GB ...