80
Fig. 37
1.
Disconnect the leads from the flue gas temperature
sensor.
10
1
10
30
50
70
90
110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance
in kΩ
Fig. 38
Sensor type: NTC 10 k
Ω
2.
Check the sensor resistance and compare it with
the curve.
3.
In the event of severe deviation replace the sensor.
Checking the fuse
Note
Switch OFF the power supply.
Maintenance
Checking the flue gas temperature sensor
(cont.)