34
Coding
Coding in the delivered condition
Possible change
System design
00:1
System version 1:
One heating circuit without mixer
A1 (heating circuit 1), without DHW
heating
00:2
to
00:10
For system schemes, see the follow-
ing table:
Value, ad-
dress 00: ...
Description
2
1 heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automatical-
ly)
3
1 heating circuit with mixer M2 (heating circuit 2), without DHW heating
4
1 heating circuit with mixer M2 (heating circuit 2), with DHW heating
5
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), without DHW heating (code is set automatically)
6
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), with DHW heating (code is set automatically)
7
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), without DHW heating
8
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), with DHW heating
9
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), without DHW heating (code is set
automatically)
10
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), with DHW heating (code is set au-
tomatically)
System examples
Coding in the delivered condition
Possible change
Code 1
77:1
LON subscriber number, if LON
communication module is installed
77:2
to
77:99
LON subscriber number, adjustable
from 1 to 99:
1 = Boiler
2 - 9 = Do not adjust
10 - 90 = Vitotronic 200-H
Note
Allocate each number
only
once.
Detached house/apartment building
7F:1
Detached house
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
Code 1
General/Group "1"