Rated voltage
230 V
Rated frequency
50 Hz
Protection class
I
Permissible ambient temper-
ature
■
Operation
0 to +40 °C
■
Storage and transport
-20 to +65 °C
Backup fuse (power supply)
max. 16 A
Rated heating output range
TF/TR = 50/30
kW
16 - 80 32 - 120 32 - 160 48 - 200 48 - 240 64 - 280
64 - 318
TF/TR = 80/60
kW
15 - 74 29 - 110 29 - 146 44 - 184 44 - 220 58 - 258
58 - 291
Rated heat input
kW
76
113
151
189
226
264
300
Product ID
CE-0085CR0391
Permiss. operating temper-
ature
°C
95
Permiss. flow temperature
(= safety temperature)
°C
110
Max. permiss. operating
pressure
bar
6
MPa
0.6
Min. permiss. operating
pressure
bar
0.5
MPa
0.05
Test pressure
bar
7.8
MPa
0.78
Boiler body dimensions
Length/handling dimension
*2
mm
660/450 780/570 780/570
900
900
1010
1010
Width
mm
680
680
680
680
680
680
680
Height
mm
1459
1459
1459
1459
1459
1459
1459
Overall dimensions without
boiler flue connection
Length g
mm
745
875
875
980
980
1090
1090
Width c
mm
750
750
750
750
750
750
750
Height a
mm
1500
1500
1500
1500
1500
1500
1500
Foundation dimensions
Length
mm
750
850
850
1000
1000
1100
1100
Width
mm
800
800
800
800
800
800
800
Height
mm
100
100
100
100
100
100
100
Weight
Overall unit weight
kg
238
295
295
340
340
385
385
Packed unit
kg
288
345
345
390
390
435
435
Boiler body
kg
183
230
230
265
265
300
300
Boiler body with transport
pallet
kg
210
260
260
295
295
330
330
Burner
kg
10
11
11
15
15
15
15
Water capacity
l
65
103
103
145
145
180
180
*2
With unassembled base rail
Specification
Vitocrossal 100 specification
5792 925 GB