79
10
1
10
30
50
70
90
110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance
in kΩ
Fig. 36
Sensor type: NTC 10 k
Ω
2.
Check the sensor resistance and compare it with
the curve.
3.
In the event of severe deviation replace the sensor.
Checking the flue gas temperature sensor
Note
The boiler water temperature sensor is a dual sensor.
The flue gas temperature sensor locks out the boiler if
the permissible flue gas temperature is exceeded.
After the flue system has cooled down, press reset
button
R
to cancel the lock.
Maintenance
Checking the boiler water temperature sensor
(cont.)
5792 925 GB