77
X3
2.
1.
3.
Fig. 31
3.
Disconnect plug "X3" from the control unit.
100
10
-20
-10
0
10
20
30
Temperature in °C
6
8
20
40
60
80
200
Resistance
in kΩ
Fig. 32
Sensor type: NTC 10 k
Ω
4.
Measure the resistance of the outside temperature
sensor across terminals "X3.1" and "X3.2" on the
disconnected plug. Compare with the curve.
5.
If the results are very different from the curve, dis-
connect the wires from the sensor. Repeat the test
directly on the sensor.
6.
Depending on the result, replace the lead or the
outside temperature sensor.
Maintenance
Checking the outside temperature sensor
5792 925 GB
Maintenance
Содержание Vitocrossal 100 CI1
Страница 119: ...119 Up to 80 kW Fig 67 Connection and wiring diagram Connection and wiring diagram cont 5792 925 GB Appendix ...
Страница 138: ...138 5792 925 GB ...
Страница 139: ...139 5792 925 GB ...