74
Fault code dis-
played
System characteristics
Cause
Measures
DE
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Check room temperature sensor
for heating circuit 2 and the remote
control settings.
DF
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 3 (with mixer)
Check room temperature sensor
for heating circuit 3 and the remote
control settings.
E0
Control mode
External LON subscriber
error
Check connections and LON sub-
scribers.
E1
Burner in a fault state
Ionisation current too high
during calibration
Check gap between ionisation
electrode and burner gauze as-
sembly (see page 21).
In open flue operation, prevent
high levels of dust in the combus-
tion air.
Press reset button
R
.
E3
Burner in a fault state
Heat transfer too low dur-
ing calibration.
Temperature limiter has
shut down.
Ensure adequate heat transfer.
Press reset button
R
.
E4
Burner blocked
24 V power supply fault
Replace control unit.
E5
Burner blocked
Flame amplifier fault
Replace control unit.
E7
Burner in a fault state
Ionisation current too low
during calibration
Check ionisation electrode for the
following:
■
Distance to burner gauze assem-
bly (see page 21)
■
Contamination on electrode
■
Connecting cable and plug-in
connections
Check flue system; remove flue
gas recirculation if required.
Press reset button
R
.
E8
Burner in a fault state
Ionisation current lies out-
side the permissible range
Check gas supply (gas pressure
and gas flow switch), gas train and
connecting cable.
Check ionisation electrode for the
following:
■
Distance to burner gauze assem-
bly (see page 21)
■
Contamination on electrode
Press reset button
R
.
EA
Burner in a fault state
Ionisation current not with-
in permissible range dur-
ing calibration (excessive
deviation from previous
level)
Check flue system; remove flue
gas recirculation if required.
In open flue operation, prevent
high levels of dust in the combus-
tion air.
Press reset button
R
.
Following several unsuccessful re-
set attempts, replace the coding
card and press reset button
R
.
Troubleshooting
Fault codes
(cont.)
5792 925 GB
Diagnosis