52
Coding in the delivered condition
Possible change
99:0
Never adjust
9A:0
Never adjust
9b:70
Set flow temperature for external
demand 70 °C
9b:0
to
9b:127
Set flow temperature for external de-
mand adjustable from 0 to 127 °C
(limited by boiler-specific parame-
ters)
9C:20
Monitoring LON subscribers.
If there is no response from a sub-
scriber for 20 min, the values
specified in the control unit are
used. Only then will a fault mes-
sage be issued.
9C:0
No monitoring
9C:5
to
9C:60
Time adjustable from 5 to 60 min
9F:8
Differential temperature 8 K; only
in conjunction with a heating circuit
with mixer
9F:0
to
9F:40
Differential temperature adjustable
from 0 to 40 K
Boiler
Coding
Coding in the delivered condition
Possible change
04:1
Minimum burner pause time sub-
ject to boiler load (specified by
boiler coding card)
04:0
Minimum burner pause time set per-
manently (specified by boiler coding
card)
06:...
Maximum limit of the boiler water
temperature, specified in °C by
boiler coding card
06:20
to
06:127
Maximum limit of boiler water tem-
perature within the ranges specified
by the boiler
0d:0
Never adjust.
0E:0
Never adjust.
21:0
No service interval set (in hours
run)
21:1
to
21:100
The number of hours run before the
burner should be serviced is adjust-
able from 100 to 10,000 h
One adjusting step
≙
100 h
23:0
No time set for burner service in-
terval
23:1
to
23:24
Time interval adjustable from 1 to
24 months
24:0
"Service"
not shown on the dis-
play
24:1
"Service"
is shown on the display
(address is automatically set and
must be manually reset after a serv-
ice has been carried out)
29:0
Burner fuel consumption: no me-
tering
29:1
to
29:255
Entry of 0.1 to 25.5; 1 step
≙
0.1 l or
gallon/h
2E:0
Never adjust.
2F:0
Venting program/filling program
disabled
2F:1
Venting program enabled
2F:2
Filling program enabled
30:1
Internal variable speed circulation
pump (set automatically)
30:0
Internal circulation pump not speed-
controlled (e.g. temporarily for serv-
ice)
Codes
Coding level 2
(cont.)
5686 293 GB
Codes
Содержание J3HA
Страница 10: ...10 2x 1 2 4 3 Fig 2 Installation sequence Mounting the boiler and making connections 5686 293 GB Installation ...
Страница 21: ...21 2 3 2x 1 Fig 14 Installation sequence Fitting the front panel 5686 293 GB Installation ...
Страница 78: ...78 Troubleshooting Maintenance cont 5686 293 GB Diagnosis ...
Страница 90: ...90 0004 0006 0005 0003 0001 0002 Fig 51 Parts lists Miscellaneous assembly 5686 293 GB Components ...
Страница 114: ...114 5686 293 GB ...
Страница 115: ...115 5686 293 GB ...