Heating circuit 1, heating circuit 2, heating circuit 3
Coding
Coding in the delivered condition
Possible change
Economy function outdoor temperature
A5:5
With heating circuit pump logic
function (economy control): Heat-
ing circuit pump is "OFF" when the
outside temperature (OT) is 1 K
higher than the set room tempera-
ture (RT
set
)
OT
>
RT
set
+ 1 K
A5:0
Without heating circuit pump logic
function
A5:1
to
A5:15
With heating circuit pump logic func-
tion: heating circuit pump "OFF"
(see the following table)
Parameter address A5: ...
With heating circuit pump logic function: heating circuit pump "OFF"
1
OT
>
RT
set
+ 5 K
2
OT
>
RT
set
+ 4 K
3
OT
>
RT
set
+ 3 K
4
OT
>
RT
set
+ 2 K
5
OT
>
RT
set
+ 1 K
6
OT
>
RT
set
7
to
OT
>
RT
set
- 1 K
15
OT
>
RT
set
- 9 K
Coding in the delivered condition
Possible change
Extended economy function dampened outdoor temp.
A6:36
Extended economy mode
disa-
bled
A6:5
to
A6:35
Extended economy mode active.
The burner and heating circuit pump
will stop at a variable value, adjusta-
ble between 5 and 35 °C plus 1 °C.
Mixer is being closed. The basis for
this is the adjusted outside tempera-
ture. This is composed of the actual
outside temperature and a time con-
stant that takes account of the way
an average building cools down.
Extended economy function mixing valve
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
■
If the mixer has been trying to
close for longer than 20 min.
Heating circuit pump "ON":
■
If the mixer changes to control
function
■
If there is a risk of frost
Pump idle time, transition reduced mode
A9:7
With pump idle time: heating circuit
pump "OFF" if set value is modi-
fied by changing the operating
mode or changing the set room
temperature
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time, adjustable from
1 to 15. The higher the value, the
longer the pump idle time.
Codes
Coding level 1
(cont.)
5686 293 GB
Codes
Содержание J3HA
Страница 10: ...10 2x 1 2 4 3 Fig 2 Installation sequence Mounting the boiler and making connections 5686 293 GB Installation ...
Страница 21: ...21 2 3 2x 1 Fig 14 Installation sequence Fitting the front panel 5686 293 GB Installation ...
Страница 78: ...78 Troubleshooting Maintenance cont 5686 293 GB Diagnosis ...
Страница 90: ...90 0004 0006 0005 0003 0001 0002 Fig 51 Parts lists Miscellaneous assembly 5686 293 GB Components ...
Страница 114: ...114 5686 293 GB ...
Страница 115: ...115 5686 293 GB ...