47
Coding in the delivered condition
Possible change
Duration set flow temperature increase
Fb:30
Duration for raising the set boiler
water temperature or set flow tem-
perature (see coding address "FA")
60 min. See example on
page 101.
Fb:0
to
Fb:150
Duration adjustable from 0 to
300 min;
1 step
≙
2 min
Coding level 2
Calling up coding level 2
■
In coding level 2
all
codes are accessible.
■
Codes that are not assigned, due to the heating sys-
tem equipment level or the setting of other codes,
are not displayed.
■
Below, the heating circuit without mixer is designated
"Heating circuit 1"
and the heating circuits with
mixer as
"Heating circuit 2"
or
"Heating circuit 3"
.
If the heating circuits were given individual designa-
tions, the selected designation and
"HC1"
,
"HC2"
or
"HC3"
appear instead.
The codes are divided into groups
■
"General"
■
"Boiler"
■
"DHW"
■
"Solar"
■
"Heating circuit 1/2/3"
■
"All codes std device"
In this group, all coding addresses (except the cod-
ing addresses from the
"Solar"
group) are displayed
in ascending order.
■
"Standard setting"
Call up code 2
Service menu:
1. Press
OK
and
simultaneously for approx. 4 s.
2. Press
OK
and simultaneously for approx. 4 s.
3.
"Coding level 2"
4. Select group of required coding address.
5. Select coding address.
6. Set the value according to the following tables and
confirm with
OK
.
Resetting all codes to the factory setting
Select
"Standard setting"
.
Note
This also resets codes at coding level 1.
General
Coding
Coding in the delivered condition
Possible change
00:1
System version 1:
One heating circuit without mixer
(A1), without DHW heating
00:2
to
00:10
For system schemes, see the follow-
ing table:
Value, ad-
dress 00: ...
System ver-
sion
Description
2
1
One heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is
set automatically)
3
2, 3
One heating circuit with mixer M2 (heating circuit 2), without DHW heating
4
2, 3
One heating circuit with mixer M2 (heating circuit 2), with DHW heating
5
2, 3, 4
One heating circuit without mixer A1 (heating circuit 1) and one heating circuit with
mixer M2 (heating circuit 2), without DHW heating (code is set automatically)
Codes
Coding level 1
(cont.)
5686 293 GB
Codes
Содержание J3HA
Страница 10: ...10 2x 1 2 4 3 Fig 2 Installation sequence Mounting the boiler and making connections 5686 293 GB Installation ...
Страница 21: ...21 2 3 2x 1 Fig 14 Installation sequence Fitting the front panel 5686 293 GB Installation ...
Страница 78: ...78 Troubleshooting Maintenance cont 5686 293 GB Diagnosis ...
Страница 90: ...90 0004 0006 0005 0003 0001 0002 Fig 51 Parts lists Miscellaneous assembly 5686 293 GB Components ...
Страница 114: ...114 5686 293 GB ...
Страница 115: ...115 5686 293 GB ...