15
Outside temperature sensor
!
For fitting the wireless outside temperature sensor
(wireless accessory):
Wireless base station installation and service
instructions
Fitting location for outside temperature sensor
■
North or north-western wall, 2 to 2.5 m above ground
level; in multi storey buildings, in the upper half of the
second floor
■
Not above windows, doors or vents
■
Not immediately below balconies or gutters
■
Never render over
Outside temperature sensor connection
2-core lead, length max. 35 m with a cross-section of
1.5 mm
2
External demand via switching contact
Connection options:
■
EA1 extension (accessory, see separate installation
instructions)
■
Plug
lH
When the contact is closed, burner operation is load-
dependent. The boiler water is heated to the set value
selected in coding address "9b" in group
"General"/1
.
The boiler water temperature is limited by this set
value and by the electronic maximum limit (coding
address "06" in group
"Boiler"/2
).
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection
must be floating
and
meet the requirements of protection class II.
Plug
lH
EA1 extension
A
lH
N
?
1 L
A
Floating contact (when connected, remove jumper
between L and 1)
B
[{S
DE
[{D
DE
[{A
DE
A
A
Floating contact
B
EA1 extension
Codes
■
"4b:1" in group
"General"/1
■
Effect of the function on the relevant heating circuit
pump:
coding address "d7" in group
"Heating circuit"
(only
for weather-compensated control units)
■
Effect of the function on the circulation pump for cylin-
der heating:
coding address "5F" in group
"DHW"/3
Codes
■
Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) to 2 in
group
"General"/1
■
Effect of the function on the relevant heating circuit
pump:
coding address "d7" in group
"Heating circuit"
(only
for weather-compensated control units)
■
Effect of the function on the circulation pump for cylin-
der heating:
coding address "5F" in group
"DHW"/3
External demand via 0
–
10 V input
Connection at 0
–
10 V input at
EA1 extension
.
Installation sequence
Electrical connections
(cont.)
5686 293 GB
Installation
Содержание J3HA
Страница 10: ...10 2x 1 2 4 3 Fig 2 Installation sequence Mounting the boiler and making connections 5686 293 GB Installation ...
Страница 21: ...21 2 3 2x 1 Fig 14 Installation sequence Fitting the front panel 5686 293 GB Installation ...
Страница 78: ...78 Troubleshooting Maintenance cont 5686 293 GB Diagnosis ...
Страница 90: ...90 0004 0006 0005 0003 0001 0002 Fig 51 Parts lists Miscellaneous assembly 5686 293 GB Components ...
Страница 114: ...114 5686 293 GB ...
Страница 115: ...115 5686 293 GB ...