101
Displayed fault
code
System characteristics
Cause
Measures
F.468
Burner in a fault state
Ionisation current too high
during calibration
Check gap between ionisation
electrode and burner gauze as-
sembly.
Heat generator installation
and service instructions
Check whether there is a lot of
dust in the ventilation air (e.g. from
construction work).
Reset the appliance.
Note
Deposits on the electrodes indicate
foreign bodies in the ventilation air.
Check the installation room and
flue system for causes of the de-
posits. For example: Laundry de-
tergents, cleaning agents, toilet-
ries, deposits in the ventilation air
supply (chimney).
If burner gauze assembly and ioni-
sation electrode have been re-
placed, also clean fan unit, gas/air
channel and Venturi extension.
F.471
No heat demand
System pressure sensor
not available, lead break
or short circuit
■
Check system pressure sensor
(plug
aND
).
■
Check lead and plug-in connec-
tion.
■
Measure, to see if supply voltage
to sensor is 5 V
–
.
F.473
No heat demand
HMU heat management
unit communication error
Check connecting cable between
burner control unit and HMU heat
management unit.
F.474
Burner in a fault state
Error in scheduled pro-
gram run monitoring
Reset the appliance.
If fault occurs repeatedly, replace
BCU burner control unit (see
page 109).
F.517
Control mode, remote control
unit not functioning
Lead break, PlusBus ca-
ble, incorrect appliance
address set, remote con-
trol faulty
■
Check setting in commissioning
assistant.
■
Check remote control cable.
■
Check remote control subscriber
number. Replace faulty remote
control if applicable.
F.527
Burner in a fault state
Incorrect parameter set,
HMU heat management
unit
Overwrite (flash) the HMU heat
management unit with the correct
parameter set, see page 109.
F.528
Burner in a fault state
Incorrect parameter set,
BCU burner control unit
Overwrite (flash) the BCU burner
control unit with the correct param-
eter set, see page 109.
F.530
Solar function limited
Sensor value not available
or lead break of one or
more sensors/missing
sensor(s)
Check sensor(s), or connect miss-
ing sensor(s) to SDIO electronics
module.
Troubleshooting
Fault messages
(cont.)
5593201
Diagnosis
Содержание B2HF
Страница 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Страница 45: ...45 1 2x 1 2 3 2x 2 3 Fig 32 Commissioning inspection maintenance Removing the front panel 5593201 ...
Страница 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Страница 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...