83
0
4.
Use
to confirm.
0
5. "Actuator test"
0
6.
to confirm the security prompt.
Note
If an actuator function is not possible due to the
running process, the function is interrupted. A
message appears.
0
7.
Use / to select the required group. See the
table below.
0
8.
Tap the required actuator function. Several func-
tions can be activated simultaneously.
0
9.
If necessary, tap
to confirm. The functions are
active for 30 s.
10.
Use
to end the Actuator test.
The following actuator functions can be controlled subject to the system equipment level:
Display
Explanation
Gas condensing boiler group
Fan speed
Set value
Burner fan speed in rpm (rotations/minute)
Burner modulation, set
value
■
Off
■
Minimum
heating out-
put
■
Maximum
heating out-
put
■
Maximum
DHW output
Modulation level (in accordance with specific heat generator settings)
3-way valve target posi-
tion
Heating
3-way diverter valve set to heating mode
Middle
3-way diverter valve in central position (filling/draining)
DHW
3-way diverter valve set to DHW heating
Heating group
Primary circuit pump
speed
Set value
Internal circulation pump speed in %
3-way valve target posi-
tion
Heating
3-way diverter valve set to heating mode
Middle
3-way diverter valve in central position (filling/draining)
DHW
3-way diverter valve set to DHW heating
Heating circuit 1 pump
speed
Set value
Speed, heating circuit pump, heating circuit 1 without mixer in %
Heating circuit 2 pump
speed
Set value
Speed, heating circuit pump, heating circuit 2 with mixer in %
Heating circuit 3 pump
speed
Set value
Speed, heating circuit pump, heating circuit 3 with mixer in %
Heating circuit 4 pump
speed
*2
Set value
Speed, heating circuit pump, heating circuit 4 with mixer in %
Mixer HC2
Open
Output for "Mixer open" enabled (mixer extension kit)
Stop
Current position is maintained
Close
Output for "Mixer close" enabled
Mixer HC3
Open
Output for "Mixer open" enabled (mixer extension kit)
Stop
Current position is maintained
Close
Output for "Mixer close" enabled
Mixer HC4
*2
Open
Output for "Mixer open" enabled (mixer extension kit)
Stop
Current position is maintained
Close
Output for "Mixer close" enabled
DHW group
*2
(only Vitodens 200-W, type B2HF with 7 inch screen)
Diagnosis and service checks
Checking outputs (actuator test)
(cont.)
5593201
Diagnosis
Содержание B2HF
Страница 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Страница 45: ...45 1 2x 1 2 3 2x 2 3 Fig 32 Commissioning inspection maintenance Removing the front panel 5593201 ...
Страница 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Страница 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Страница 135: ...135 5593201 ...