27
Assigning functions in the commissioning assis-
tant
See commissioning assistant in "Commissioning".
Information on connecting PlusBus subscribers
Only the following PlusBus subscribers can be connec-
ted to the control:
■
2 x EM-M1 or EM-MX extensions (ADIO electronics
module)
■
2 Vitotrol 200-E
■
3 x EM-EA1 extensions (DIO electronics module)
■
1 x EM-S1 extension (ADIO or SDIO/SM1A electron-
ics module)
■
1 x EM-P1 extension (ADIO electronics module)
The max. total length of the PlusBus lead is 50 m.
With an unscreened lead, 2-core, 0.34 mm
2
.
Checking the CAN bus terminator switch setting
The CAN bus resistor is switched using switch
A
in
the wiring chamber.
1
91
91
ON
A
Fig. 18
■
If the device is
not
integrated into a CAN bus sys-
tem:
Switch
A
must
not
be set to "ON".
■
If the device is integrated into a CAN bus system and
is located at the beginning or end of this system (not
in the middle) of the CAN bus system (connected to
only one plug
lA
): Set switch
A
to "ON".
C
C
A
91 91
B
B
ON
Fig. 19
A
Heat generator / HMU heat management unit
B
CAN bus cable
C
CAN bus other subscribers
■
If the device is integrated into a CAN bus system and
is
not
located at the beginning or end of the CAN
bus system (both plugs
lA
connected): Do
not
set
switch
A
to "ON".
A
C
C
B
B
91 91
ON
Fig. 20
Power supply for accessories at plug
lH
/
aBH
(230 V ~)
When positioned in wet rooms, accessories outside
the wet area must not be connected to the power sup-
ply at the HMU heat management unit. If the boiler is
not sited in a wet room, the power supply for accesso-
ries can be connected directly to the HMU heat man-
agement unit. This connection is switched directly with
the ON/OFF switch of the appliance.
If the total system current exceeds 6 A, connect one or
more extensions directly to the mains supply via an
ON/OFF switch (see next chapter).
Installation sequence
Electrical connections
(cont.)
5593201
Installation
Содержание B2HF
Страница 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Страница 45: ...45 1 2x 1 2 3 2x 2 3 Fig 32 Commissioning inspection maintenance Removing the front panel 5593201 ...
Страница 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Страница 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Страница 135: ...135 5593201 ...