82
The messages are sorted by date.
Tap the following buttons:
1.
" "
2. "Service"
3.
Enter password
"viservice"
.
4.
Use
to confirm.
5. "Message history"
The following is displayed in the message lists:
■
Date and time of the occurrence of the notifica-
tion
■
Notification number
■
Description of the notification
■
Subscriber number of the component on which
the message has occurred:
PlusBus subscriber components
0
EM-S1 extension (ADIO electronics
module)
1 - 15
EM-M1, EM-MX and EM-P1 extensions
(ADIO electronics module)
17 - 31 EM-EA1 extension (DIO electronics
module)
32 - 47 Cylinder module (electronics module
M2IO)
49 - 63 Vitotrol 200-E
64
SDIO/SM1A electronics module
CAN BUS subscriber components
1
HMU heat management unit
50 BCU burner control unit
58 RF module (wireless module)
59 HMI programming unit
60 Fan unit
90 Gateway
Low power radio subscriber components
49 - 63 Vitotrol 300-E
6.
■
"Faults"
to call up saved fault messages. For
further details, see the following chapter "Fault
messages".
■
"Service messages"
to call up saved service
messages.
P.1 Maintenance due after interval
P.4 Top up heating water.
P.8 Maintenance due after burner hours run.
■
"Status"
, to call up the saved status messages.
S.60 Summer mode active (outside temperature
economy function)
S.74 Heating suppression, heating
S.75 DHW circulation pump active
■
"Warnings"
to call up saved warning messages.
A.11 System pressure has fallen below the
standard range
Measure: Check system pressure and dia-
phragm expansion vessel. Check settings
for set system pressure and range in the
commissioning assistant.
A.12 Real time clock battery flat.
Measure: Replace the battery
(type CR2032) in the HMU heat manage-
ment unit.
A.18 Possible condensate backup in the heat
cell
Measure: Check the combustion chamber
and condensate drain.
A.20 Service interval could not be activated.
Measure: Check the time and date set-
tings.
A.21 System pressure has exceeded maximum
pressure.
Measure: Check safety valve and dia-
phragm expansion vessel.
On combi boilers: Check plate heat
exchanger
■
"Information"
, to call up saved service informa-
tion.
I.56 External demand active
I.57 External blocking active
I.59 Parameters have been restored (parameter
set was flashed to BCU electronics mod-
ule).
7.
If you wish to delete the messages, tap .
8.
to confirm
Checking outputs (actuator test)
Note
When the actuator test is started, all actuators are ini-
tially disabled and valves moved to their central posi-
tion.
Tap the following buttons:
0
1.
" "
0
2. "Service"
0
3.
Enter password
"viservice"
.
Diagnosis and service checks
Calling up messages (message history)
5593201
Diagnosis
Содержание B2HF
Страница 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Страница 45: ...45 1 2x 1 2 3 2x 2 3 Fig 32 Commissioning inspection maintenance Removing the front panel 5593201 ...
Страница 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Страница 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Страница 135: ...135 5593201 ...