background image

I-VICFLEX.AB1/AB2/AB10_2

REV_R

I-VICFLEX.AB1/AB2/AB10 

/ Victaulic

®

 VicFlex

 Styles AB1/AB2/AB10 Brackets / Installation Instructions

IMPORTANT INSTALLATION INFORMATION

• Victaulic

®

 VicFlex

 products shall be installed according to 

current, applicable National Fire Protection Association (NFPA 
13, 13D, 13R, etc.) standards or equivalent standards and in 
accordance with applicable building and fire codes. Victaulic

®

 

VicFlex

 products are intended to be installed in wet, dry, or 

preaction actuated systems. Deviations from these standards or 
alterations to Victaulic

®

 VicFlex

 products or sprinklers will void 

any Victaulic warranty and will impact system integrity. Installations 
shall meet the provisions of the local authority having jurisdiction 
and local codes, as applicable, and shall comply with all design 
specifications.

•   Drop ceiling construction shall meet the requirements of ASTM 

C635 and shall be installed in accordance with ASTM C636.

• Victaulic

® 

VicFlex

 Sprinkler Fittings and Style AB1, AB2, or AB10 

Brackets shall not be intermixed with other manufacturer’s flexible 
sprinkler products.

• 

When using recessed sprinklers, the standard long elbow reducer 
is recommended.

• 

Refer to the specific Victaulic product publication for 
applications and listing information. In addition, when installing 
Victaulic FireLock

®

 Automatic Sprinklers with Victaulic

®

 

VicFlex

 Sprinkler Fittings, refer to the I-40 Installation and 

Maintenance Instructions for details on sprinkler installation 
requirements. Product publications and installation instructions 
can be downloaded at victaulic.com.

• 

Size the piping system to meet or exceed the minimum required 
flow rate for the sprinkler system.

• 

Per NFPA requirements, flush the system to remove foreign 
material. Continue to flush the system until water runs clear.

• 

DO NOT

 install sprinkler system piping through heating ducts.

• 

DO NOT

 connect sprinkler system piping to domestic hot water 

systems.

• 

DO NOT

 allow electrical wiring or other cabling to be hung or 

wrapped around the sprinkler piping system.

• 

DO NOT

 install sprinklers and sprinkler fittings where ambient 

conditions may fall below or exceed the maximum listed or 
approved temperature ratings.

• 

The flexible hose shall not be bent or fluctuated up-and-down or 
side-to-side when pressurized.

• 

Victaulic VicFlex flexible hoses may be painted or coated, provided 
that the paint or coating is compatible with stainless steel material. 
Care shall be taken to ensure that the sprinkler and associated 
components are not painted.

• 

Flexible hose and fittings have limited flexibility* and are 
intended only to be installed with bends not less than their 
respective minimum bend radii. DO NOT install flexible hose in 
a straight configuration.

• 

Protect wet piping systems from freezing temperatures.

• 

If construction is altered, the building owner or their representative 
is responsible for referencing applicable standards to determine if 
additional sprinklers or other system adjustments are required.

• 

The building owner or their representative is responsible for 
maintaining the fire protection system in proper operating 
condition.

• 

After installation is complete, the entire sprinkler system shall be 
tested in accordance with applicable standards (NFPA 13, NFPA 
25, etc.) that describe the care and maintenance of sprinkler 
systems. In addition, the authority having jurisdiction may have 
additional maintenance, testing, and inspection requirements that 
shall be followed. 

NOTE:

 A successful test is not a substitute for 

proper system installation and maintenance.

 WARNING

•  Relocation of Victaulic

®

 VicFlex

™ 

products SHALL be performed 

by qualified personnel familiar with the system’s original design 
criteria, sprinkler listings/ approvals, and state and local codes 
(including NFPA 13 standards).

Failure to relocate this Victaulic

® 

VicFlex

 product properly could 

affect its performance during a fire, resulting in death or serious 
personal injury and property damage.

* Reference UL 2443: Section 25.1

INTRODUCTION

Victaulic

®

 VicFlex

 Sprinkler Fittings connect the sprinkler piping directly to the sprinkler using a flexible hose and fittings and are designed for use 

in ceiling suspension systems. Each drop assembly comes with one flexible hose, one adapter nipple or captured coupling, one sprinkler reducing 
nipple, and the Style AB1, AB2, or AB10 Bracket.

Maximum Working Pressure Rating of Flexible Hose:

    200 psi/14 Bar/1379 kPa (FM) 

    175 psi/12 Bar/1207 kPa (UL) 

    16 Bar/1600 kPa/232 psi (VdS and LPCB) 

    1.4 MPa/1400 kPa/203 psi (CCC) 

    300 psi/21 Bar/2068 kPa (FM – Series AH2-300, AH2-CC-300) 

    300 psi/21 Bar/2068 kPa (UL – Series AH2-300, AH2-CC-300)

Maximum Ambient Temperature Rating of Flexible Hose:

    225° F/107° C (UL, FM, VdS, LPCB) 
    135° C/275° F (CCC – Series AH3, AH4) 
    150° F/66° C (UL – Series AH2-CC-300)

Connection to Sprinkler Piping:

  1 inch/DN25 NPT/BSPT (UL, FM, CCC) 

    1 inch/DN25 IGS (UL, FM, VdS) 

    DN20/3/4 inch BSPT (VdS) 

    DN32/1 1/4 inch BSPT (LPCB)

Minimum Bend Radius of Flexible Hose:

 

3 inch/76 mm (UL – Series AH1, AH1-CC, AH2-300, 

 AH2-CC-300) 

2 inch/50 mm (UL – Series AH2, AH2-CC) 

7 inch/178 mm (FM – Series AH1, AH1-CC, AH2, AH2-CC, AH3,  

 

AH4, AH2-638) 

76 mm/3 inch (VdS – Series AH1, AH1-CC, AH2, AH2-CC, AH3,  

 AH4) 

76 mm/3 inch (LPCB – Series AH1, AH1-CC, AH2, AH2-CC) 

178 mm/7 inch (CCC – Series AH1, AH2, AH3, AH4) 

8 inch/203 mm (FM – Series AH2-300, AH2-CC-300)

Maximum K-Factor of Sprinkler to be Connected to Sprinkler 

Reducing Nipple:

  Refer to footnotes in the “Friction Loss Data” section

Maximum Number of 90° Bends Per Flexible Hose:

 

Refer to the “Friction Loss Data” section

Flexible Hose Bend Characteristics:
 NOTE:

 Care shall be taken to avoid torquing the flexible hose.

90°

OR

OR

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

Minimum 

Bend Radius

2X

Minimum 

Bend

Radius

2X

Minimum 

Bend

Radius

SCAN QR CODE FOR ACCESS TO THE FULL 

I-VICFLEX.BRG BEND RADIUS GUIDE INSTRUCTIONS 

ON VICTAULIC.COM

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...

Страница 18: ...REGIONAL AVAILABILITY ONLY Model Length of Flexible Hose inches mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH4 31 31 790 1 2...

Страница 19: ...nd AB10 Brackets AMF Armstrong Chicago Metallic Dipling Durlum Geipel Gema Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow Fischer USG Donn Other manufacturers ceili...

Страница 20: ...9 9 75 3 AH1 72 1830 72 14 26 25 98 46 8 85 2 178 mm 7 inch minimum bend radius Friction loss data is in accordance with GB5135 16 Corresponding flow rate is 113 55 liters per minute 30 gallons per mi...