background image

I-VICFLEX.AB1/AB2/AB10_11

REV_R

I-VICFLEX.AB1/AB2/AB10 

/ Victaulic

®

 VicFlex

 Styles AB1/AB2/AB10 Brackets / Installation Instructions

INSTALLATION FOR WOOD JOISTS/STUDS 

(FM ONLY FOR AB1 AND FM/UL FOR AB2)

1.

  Install the flexible hose into the sprinkler piping and the sprinkler 

reducing nipple onto the flexible hose by following the applicable 
instructions on pages 4 − 7.

2.

  Loosen the wing screw of the Style AB1 or AB2 end bracket 

assembly.

1½-inch/38-mm Long #10 

Wood Screws (4 Total)

Wing

Screw

3.

  Place the end bracket assembly (without the wing screw) against 

the inside surface of the one wood joist/stud with the square bar 
resting on top of the wood joist/stud, as shown in the graphic 
above.

3a.

  Slide the end bracket assembly (with the wing screw) toward the 

inside surface of the opposite wood joist/stud, as shown in the 
graphic above.

4.

  Install the modified Style AB1 or AB2 Bracket to the wood joists/

studs by using four, 1 1/2-inch/38-mm long #10 wood screws in the 
locations noted in the graphic shown above. 

NOTE:

 Install the top 

two wood screws first.

5. Optional:

 Tighten the wing screw on top of the end bracket 

assembly to a torque of 36 inch-lbs/4 N•m (approximately 1/2 to 3/4 
of a turn past hand-tight). 

6. 

Perform steps 2 − 2c on pages 8 − 9 to complete the installation.

NOTES:

• 

For wood joists/studs larger than 2 x 4, longer sprinkler reducing 
nipples shall be used, or one of the alternative installation methods 
on the following pages shall be followed.

• 

For the 24-inch/610-mm length Style AB2 Bracket, the maximum 
on-center spacing between wood joists/studs is 20 inches/ 
508 mm.

INSTALLATION FOR ASTM C645 METAL JOISTS/

STUDS INSTALLED IN ACCORDANCE WITH 

ASTM C754 STANDARDS 

(FM ONLY FOR AB1 AND FM/UL FOR AB2)

1.

  Install the flexible hose into the sprinkler piping and the sprinkler 

reducing nipple onto the flexible hose by following the applicable 
instructions on pages 4 − 7.

2.

  Loosen and remove the wing screw of the Style AB1 or AB2 end 

bracket assembly.

Wing Screw

1¼-inch/32-mm Long #10 Self-Drilling 

Sheet Metal Screws (4 Total)

NOTE: End Bracket with 

Wing Screw is Turned 180°

3.

  Rotate the end bracket assembly (side with the wing screw 

removed in step 2) 180

°

, as shown in the graphic above. Reinstall 

the wing screw loosely into the top of the end bracket assembly.

3a.

  Place the end bracket assembly (without the wing screw) against 

the outside surface of the metal joist/stud with the square bar 
resting on top of the metal joists/studs.

3b.

  Slide the end bracket assembly (with the wing screw) toward the 

outside, flat surface of the opposite metal joist/stud, as shown in 
the graphic above.

4.

  Install the modified Style AB1 or AB2 Bracket to the metal joists/

studs by using four, 1 1/4-inch/32-mm long #10 self-drilling sheet 
metal screws in the locations noted in the graphic shown above. 

NOTE:

 Install the top two sheet metal screws first.

5. Optional:

 Tighten the wing screw on top of the end bracket 

assembly to a torque of 36 inch-lbs/4 N•m (approximately 1/2 to 3/4 
of a turn past hand-tight).

6. 

Perform steps 2 − 2c on pages 8 − 9 to complete the installation.

NOTES:

• 

For metal joists/studs larger than 2 x 4, longer sprinkler reducing 
nipples shall be used, or one of the alternative installation methods 
on the following pages shall be followed.

• 

For the 24-inch/610-mm length Style AB2 Bracket, the maximum 
on-center spacing between metal joists/studs is 20 inches/ 
508 mm.

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...

Страница 18: ...REGIONAL AVAILABILITY ONLY Model Length of Flexible Hose inches mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH4 31 31 790 1 2...

Страница 19: ...nd AB10 Brackets AMF Armstrong Chicago Metallic Dipling Durlum Geipel Gema Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow Fischer USG Donn Other manufacturers ceili...

Страница 20: ...9 9 75 3 AH1 72 1830 72 14 26 25 98 46 8 85 2 178 mm 7 inch minimum bend radius Friction loss data is in accordance with GB5135 16 Corresponding flow rate is 113 55 liters per minute 30 gallons per mi...