background image

I-VICFLEX.AB1/AB2/AB10_4

REV_R

I-VICFLEX.AB1/AB2/AB10 

/ Victaulic

®

 VicFlex

 Styles AB1/AB2/AB10 Brackets / Installation Instructions

1-INCH/DN25 IGS CONNECTION TO THE 

SPRINKLER PIPING USING A SERIES AH1-CC, 

AH2-CC, OR AH2-CC-300 FLEXIBLE HOSE

INCORRECT - Orignal Groove System (OGS) Groove Profile

CORRECT - IGS Groove Profile

Pipe and grooves are not shown to scale

The Style 108 Coupling of the Series AH1-CC, AH2-CC, and 
AH2-CC-300 shall be used 

ONLY

 with sprinkler piping connections that 

are prepared to Victaulic IGS proprietary groove specifications. 

DO NOT

 

attempt to install the coupling on sprinkler piping connections that are 
prepared to any other groove specification. Refer to Victaulic publication 
25.14 for the IGS groove specification, which can be downloaded at 
victaulic.com.

 WARNING

•  The flexible hose shall not be bent or fluctuated up-and-down or 

side-to-side when pressurized.

Failure to follow this instruction could cause improper sprinkler 
operation, resulting in death or serious personal injury and property 
damage.

DO NOT REMOVE 

NUT/BOLT/LINKAGE FOR 

INITIAL INSTALLATION

1.  DO NOT DISASSEMBLE THE COUPLING:

 The Style 108 Coupling 

of the Series AH1-CC, AH2-CC, and AH2-CC-300 is designed so 
that the installer does not need to remove the nut, bolt, or linkage 
for initial installation. This facilitates installation by allowing the 
installer to directly insert the sprinkler piping’s grooved end into the 
coupling.

2. 

The outside surface of the sprinkler piping, between the groove 
and the end of the sprinkler piping, shall be generally free from 
indentations, projections, weld seam anomalies, and roll marks 
to ensure a leak-tight seal. All oil, grease, loose paint, dirt, and 
cutting particles shall be removed.

The sprinkler piping’s outside diameter (“OD”), groove dimensions, 
and maximum allowable flare diameter shall be within the tolerances 
published in current Victaulic IGS specifications, publication 25.14, 
which can be downloaded at victaulic.com.

3. 

Check the gasket to verify that it is suitable for the intended 
service. The color code identifies the material grade. 

Refer to 

Victaulic publication 05.01 for the color code chart, which can 
be downloaded at victaulic.com, and the “NOTICE” below for 
important gasket information.

 CAUTION

•  If any conditions listed in the "NOTICE" below are met, a thin 

coat of a compatible lubricant shall be applied only to the gasket 
sealing lips to help prevent pinching, rolling, or tearing during 
installation.

•  DO NOT use excessive lubricant on the gasket sealing lips.
Failure to use a compatible lubricant may cause gasket damage, 
resulting in joint leakage and property damage.

3a.

  If any conditions listed in the “NOTICE” below are met, apply a 

thin coat of a compatible lubricant, such as Victaulic Lubricant 
or an EPDM-compatible lubricant, only to the gasket sealing lips. 
Silicone grease may be used (silicone spray is not a compatible 
lubricant).

NOTICE

•  Gaskets for Style 108 Coupling assemblies of Series AH1-CC, 

AH2-CC, and AH2-CC-300 Flexible Hoses are pre-lubricated. 

Additional lubrication is not required for the initial installation of 

wet pipe systems that are installed at or continuously operating 

above 0°F/–18°C.

Supplemental lubrication is required only if any of the following 

conditions exist. Apply a thin coat of a compatible lubricant to 

the gasket sealing lips, as noted in step 3a on this page. It is 

not necessary to remove the gasket from the housings to apply 

additional lubricant to the gasket sealing lips.
•  If the installation or continuous operating temperature is below 

0°F/–18°C

•  If the gasket has been exposed to fluids prior to installation

•  If the surface of the gasket has a dark black or shiny appearance

•  If the gasket is being installed into a dry pipe system

•  If the system will be subjected to air tests prior to being filled 

with water

•  If the gasket was involved in a previous installation
Lubricated gaskets will not enhance sealing capabilities on 

adverse sprinkler piping conditions. Sprinkler piping condition 

and preparation shall conform to the requirements listed in these 

product installation instructions.

 WARNING

•  Never leave a Style 108 Coupling of a Series AH1-CC, 

AH2-CC, or AH2-CC-300 partially assembled on grooved 
sprinkler piping. ALWAYS TIGHTEN THE HARDWARE 
IMMEDIATELY IN ACCORDANCE WITH THESE INSTRUCTIONS. 
A partially  assembled coupling poses a drop or fall hazard during 
installation and a burst hazard during testing.

•  Keep hands away from the grooved sprinkler piping and the 

openings of the coupling when attempting to insert the grooved 
sprinkler piping into the coupling.

•  Keep hands away from coupling openings during tightening.
Failure to follow these instructions could result in death or serious 
personal injury and property damage.

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...

Страница 18: ...REGIONAL AVAILABILITY ONLY Model Length of Flexible Hose inches mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH4 31 31 790 1 2...

Страница 19: ...nd AB10 Brackets AMF Armstrong Chicago Metallic Dipling Durlum Geipel Gema Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow Fischer USG Donn Other manufacturers ceili...

Страница 20: ...9 9 75 3 AH1 72 1830 72 14 26 25 98 46 8 85 2 178 mm 7 inch minimum bend radius Friction loss data is in accordance with GB5135 16 Corresponding flow rate is 113 55 liters per minute 30 gallons per mi...

Отзывы: