background image

I-VICFLEX.AB1/AB2/AB10_19

REV_R

I-VICFLEX.AB1/AB2/AB10 

/ Victaulic

®

 VicFlex

 Styles AB1/AB2/AB10 Brackets / Installation Instructions

SERIES AH1, AH1-CC, AH2, AH2-CC, AH3*, AND AH4* FLEXIBLE HOSE FRICTION LOSS DATA (VDS) 

Length of 

Flexible 

Hose 

mm/ 

inches

Outlet 

Size

Metric/ 

inches

Maximum 

Number of 

90° Bends at 

76.2-mm/3-inch 

Bend Radius

Series AH1 and AH1-CC Series AH2 and AH2-CC

Series AH3*

Series AH4*

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 20 (26,9 x 2,65)

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 25 (33,7 x 3,25)

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 20 (26,9 x 2,65)

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 25 (33,7 x 3,25)

790

31

DN15/1/2

3

4.0

12.9

5.5

18.0

5.9

19.4

5.5

18.0

DN20/3/4

915

36

DN15/1/2

3

4.6

15.0

6.4

21.0

6.9

22.5

6.4

21.0

DN20/3/4

1220

48

DN15/1/2

3

6.1

20.0

8.5

27.9

9.2

30.0

8.5

27.9

DN20/3/4

1525

60

DN15/1/2

4

7.6

25.0

10.7

35.1

11.4

37.5

10.7

35.1

DN20/3/4

1830

72

DN15/1/2

4

9.2

30.0

12.8

42.0

13.7

45.0

12.8

42.0

DN20/3/4

* SERIES AH3 AND AH4 – REGIONAL AVAILABILITY ONLY 

Series AH1, AH1-CC, AH2, AH2-CC, AH3, and AH4 Flexible Hoses are VdS Approved for use in wet systems only. 

Only VdS Approved pendent spray sprinklers of 10-mm, 15-mm, and 20-mm nominal diameters with K-factors of 57, 80, and 115 shall be used. 

Tested with a 5 3/4-inch/146-mm length straight reducer. 

When using a No. 101 90° Elbow or a No. 102 Straight Tee in place of a Style 108 Coupling on the end of a Series AH1-CC or AH2-CC Flexible Hose, the friction loss data 

shown above shall be added to the No. 101 or No. 102 friction loss data published in Victaulic publication 10.54.

The VdS Approval applies only for use with the following manufacturers’ suspended ceiling systems: 

Ceiling Suspension Systems for Styles AB1, AB2, and AB10 Brackets

AMF

Armstrong

Chicago Metallic

Dipling

Durlum

Geipel

Gema-Armstrong

Hilti

Knauf

Lafarge

Lindner

Odenwald

Richter

Rigips

Rockfon Pagos

Suckow & Fischer

USG Donn

Other manufacturers’ ceiling systems, with comparable or better performance, can be considered for approval. VdS standards for safety include, but are not limited to: 

pressure cycling, corrosion resistance, flow characteristics, vibration resistance, leakage, mechanical strength, and hydrostatic strength. Differences in equivalent lengths 

are due to varying test methods, per FM 1637 and VdS standards. Refer to these standards for additional information regarding friction loss test methods.

SERIES AH1, AH1-CC, AH2, AND AH2-CC FLEXIBLE HOSE FRICTION LOSS DATA (LPCB) 

Length of 

Flexible Hose 

mm/inches

Outlet Size

Metric/inches

Maximum Number 

of 90° Bends at 

76.2-mm/3-inch 

Bend Radius

Series AH1 and AH1-CC*

Series AH2 and AH2-CC**

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 25 (33,7 x 3,25)

Equivalent Length of 

Steel Pipe in meters/feet 

According to EN 10255 

DN 25 (33,7 x 3,25)

790

31

DN15/1/2

2

13.6

44.6

1.8

6.0

DN20/3/4

915

36

DN15/1/2

3

16.9

55.4

3.6

11.9

DN20/3/4

1220

48

DN15/1/2

3

19.9

65.1

4.3

14.0

DN20/3/4

1525

60

DN15/1/2

3

24.5

80.2

4.1

13.6

DN20/3/4

1830

72

DN15/1/2

3

28.5

93.4

5.5

18.1

DN20/3/4

  * Hose Type 2 and Size: DN20/0.8-inch Nominal ID, per LPS 1261 

** Hose Type 2 and Size: DN25/1-inch Nominal ID, per LPS 1261 

Series AH1 (104l/0l), Series AH2 (104l/02), Series AH1-CC (104l/03), and Series AH2-CC (104l/04) Flexible Hoses are LPCB Approved for use in wet systems only. 

Only LPCB Approved pendent spray sprinklers of 10-mm, 15-mm, and 20-mm nominal diameters with K-factors of 57 and 80 shall be used. 

Tested with a 5 3/4-inch/146-mm length straight reducer. 

When using a No. 101 90° Elbow or a No. 102 Straight Tee in place of a Style 108 Coupling on the end of a Series AH1-CC or AH2-CC Flexible Hose, the friction loss data 

shown above shall be added to the No. 101 or No. 102 friction loss data published in Victaulic publication 10.54.

 

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...

Страница 18: ...REGIONAL AVAILABILITY ONLY Model Length of Flexible Hose inches mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH4 31 31 790 1 2...

Страница 19: ...nd AB10 Brackets AMF Armstrong Chicago Metallic Dipling Durlum Geipel Gema Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow Fischer USG Donn Other manufacturers ceili...

Страница 20: ...9 9 75 3 AH1 72 1830 72 14 26 25 98 46 8 85 2 178 mm 7 inch minimum bend radius Friction loss data is in accordance with GB5135 16 Corresponding flow rate is 113 55 liters per minute 30 gallons per mi...

Отзывы: