background image

I-VICFLEX.AB1/AB2/AB10

INSTALLATION INSTRUCTIONS

Victaulic

®

 VicFlex

 Flexible Hose with Fittings for Fire Protection Service 

Styles AB1, AB2, and AB10 Brackets

For complete contact information, visit victaulic.com

I-VICFLEX.AB1/AB2/AB10     6829 REV R      UPDATED 09/2020      Z000AB1000

VICTAULIC AND VICFLEX ARE REGISTERED TRADEMARKS OR TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES 
IN THE UNITED STATES AND/OR OTHER COUNTRIES.                     © 2020 VICTAULIC COMPANY.                      ALL RIGHTS RESERVED.

SERIES AH1 FLEXIBLE HOSE FRICTION LOSS DATA (CCC) 

Model

Length of Flexible Hose 

mm/inches

Equivalent Length – meters/feet

Straight Configuration

Bend Configuration

AH1-31

790

31

4.78

5.80

15.7

19.0

AH1-36

915

36

5.59

10.15

18.3

33.3

AH1-48

1120

48

9.75

16.25

32.0

53.3

AH1-60

1525

60

12.15

22.94

39.9

75.3

AH1-72

1830

72

14.26

25.98

46.8

85.2

178-mm/7-inch minimum bend radius 

Friction loss data is in accordance with GB5135.16. Corresponding flow rate is 113.55 liters per minute/30 gallons per minute.

SERIES AH2 FLEXIBLE HOSE FRICTION LOSS DATA (CCC) 

Model

Length of Flexible Hose 

mm/inches

Equivalent Length – meters/feet

Straight Configuration

Bend Configuration

AH2-31

790

31

0.87

2.70

2.9

8.9

AH2-36

915

36

1.00

2.80

3.3

9.2

AH2-48

1120

48

2.23

4.66

7.3

15.3

AH2-60

1525

60

2.90

6.50

9.5

21.3

AH2-72

1830

72

3.31

7.16

10.9

23.5

178-mm/7-inch minimum bend radius

SERIES AH3 FLEXIBLE HOSE FRICTION LOSS DATA (CCC) – REGIONAL AVAILABILITY ONLY 

Model

Length of Flexible Hose 

mm/inches

Equivalent Length – meters/feet

Straight Configuration

Bend Configuration

AH3-31

790

31

5.19

7.91

17.0

26.0

AH3-36

915

36

6.17

9.92

20.2

32.6

AH3-48

1120

48

8.93

14.55

29.3

47.7

AH3-60

1525

60

11.10

20.03

36.4

65.7

AH3-72

1830

72

13.43

23.64

44.1

77.6

178-mm/7-inch minimum bend radius

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...