7

STATE-200 General Description_Rev. 0

2.

GENERAL DESCRIPTION OF THE STATE-200 UNIT

The STATE-200 unit is an acquisition extension for the ZOOM Controller for measuring and monitoring slow-
evolving signals. The ZOOM platform and ZOOM Look software plug-in must be installed on the ZOOM
Controller to allow functionalities such as data acquisition, data storage, alarm processing, and notification of
triggered alarm on the ZOOM Controller screen. 

The STATE-200 is 3U in size, like other products offered by VibroSystM such as the ZPU-5000 and PCU-
5000. The communication interface between the STATE-200 and ZOOM Controller uses an Ethernet
10/100Mbps standard transmission network.  Cat 6 STP network cable must be used.  This cable allows
installation of the unit at a distance of up to 100m from its network switch. The STATE-200 and ZOOM
Controller can share a network with other VibroSystM instruments also using Ethernet transmission.  Each
STATE-200 Unit has 16 input channels, and several STATE-200 units can be installed on a same network.

Several types of input modules are available, covering most of the parameters used in the surveillance of
rotating machines (see below, Table 1: Summary of Available Modules for the STATE-200). The modularity
of the instrument allows installation of several different types of modules on a single Unit.  Measurements
taken through this acquisition unit will be synchronized with measurements taken through other VibroSystM
instruments, thus simplifying the analysis work. We can also use this data to assist in the interpretation of
dynamic measurements (taken with ZPU-5000), or trigger measurements under various operation modes
(conditional measurements).

Table 1: Summary of Available Modules for the STATE-200

Model

Module Type

AD2T

0 to 20 mA isolated

AD3

4 - 20 mA

AD3T

4 - 20 mA isolated

AD6

0 to 5 V

DC

AD6T 

0 to 5 V

DC 

isolated

AD7

0 to +10 V

DC

, or contact closure (switch, relay, or other)

AD9T

0 to 50 mV

DC

 isolated

AD10T2

3-wire RTD PT100

Ω

 _ isolated / -50° to +350°C (-58° to + 662°F)

AD11

-5 to +5 V

DC

AD11T

-5 to +5 V

DC

 isolated

AD12

-10 to +10 V

DC

AD12T

-10 to +10 V

DC

 isolated

AD13T

0 to 100 mV

DC 

isolated

AD14T

4-wire RTD CU10

Ω

 _ isolated / -55° to +150°C (-67° to + 302°F)

AD15T

28 to 140 V

AC 

isolated

Содержание STATE-200

Страница 1: ...l P N 9423 06I0A 200 This manual divides into the following sections Section 1 General safety information Section 2 General description of the STATE 200 Unit Section 3 Installation of the STATE 200 Un...

Страница 2: ...Copyright VibroSystM Inc 2011 2 STATE 200 Installation Manual_Table of Contents Rev 0...

Страница 3: ...15 3 4 2 Protective Conductor Terminal 15 3 4 3 Ethernet Port 16 3 5 Input Modules 16 3 5 1 Input wiring and DIP switch setting 18 3 5 2 Module Installation or Replacement 22 4 USING THE STATE 200 UNI...

Страница 4: ...Copyright VibroSystM Inc 2011 4 STATE 200 Installation Manual_Table of Contents Rev 0...

Страница 5: ...be impaired Do not use this instrument in wet environments Whenever it is likely that safety protection has been impaired make this instrument inoperative and secure it against any unintended operatio...

Страница 6: ...in this manual and on this instrument Warning Danger identify conditions or practices that could cause bodily harm and result in damage to the measuring chain and other equipment to which it is conne...

Страница 7: ...TATE 200 units can be installed on a same network Several types of input modules are available covering most of the parameters used in the surveillance of rotating machines see below Table 1 Summary o...

Страница 8: ...e STATE 200 Unit main components The unit is designed to be installed in a properly ventilated rack mount enclosure Overall enclosure dimensions are 483 W x 432 D x 133 H mm 19 W x 17 D x 5 25 H inche...

Страница 9: ...and communication processor for analog I O systems This board is in communication with the ZOOM Controller to which it transmits the data that has been collected and processed through the I O modules...

Страница 10: ...I O ports for the interconnection of a sensor to its dedicated input module Each port also provide 24VDC power available for the measuring chain with an auto reset polyswitch limiting the power output...

Страница 11: ...n removable female screw terminal connector allows wiring of AC power input The STATE 200 Unit should be installed in compliance with national and local electrical code The unit relies on dual fuse pr...

Страница 12: ...Copyright VibroSystM Inc 2011 12 STATE 200 General Description_Rev 0...

Страница 13: ...exhaust ports Baffles can help to isolate exhaust air from intake air which also helps to draw cooling air through the unit The best placement of the baffles depends on the airflow patterns in the ra...

Страница 14: ...d Wiring_Rev 0 3 3 Unit installation in a 19 rack or cabinet Install side mounting brackets and adjust at the correct height In a rack with square 3 8 windows cage nuts are used Slide the unit in the...

Страница 15: ...device Mechanical characteristics Recommended wire size 1 5 mm2 16 AWG 600V rating 3 4 2 Protective Conductor Terminal The protective conductor terminal must be connected to a grounding point in compl...

Страница 16: ...reception and processing of signals from various types of sensors Input modules convert analog signals into a digital format the resulting signal is then sent to the brain board for transmission to t...

Страница 17: ...tion of input signals IN B Hi and IN B Lo Refer to Table 1 Input Modules Available on page 31 to see the type of casing for each model of input module On the backplane a small DIP switch and two pins...

Страница 18: ...If the shield on the sensor end of the cable is isolated from earth ground connect the cable shield to the ground position on the 7 position connector 1 Contact closure switch relay or other Model AD...

Страница 19: ...e casing Type A Sensor with current mA output and 24VDC input 24V COM 24VDC IN B Hi IN B Lo IN A Hi IN A Lo SW POS 1 OFF 2 ON S h i e l d N o t e T o a v o i d g r o u n d l o o p p r o b l e m s c o...

Страница 20: ...4VDC IN B Hi IN B Lo IN A Hi IN A Lo SW POS 1 OFF 2 ON 24V COM S h i e l d N o t e T o a v o i d g r o u n d l o o p p r o b l e m s c o n n e c t s h i e l d t o e a r t h g r o u n d o n o n e e n d...

Страница 21: ...Module casing Type B 3 wire 100 PT100 RTD 24VDC IN B Hi IN B Lo IN A Hi IN A Lo SW POS 1 OFF 2 OFF S h i e l d N o t e T o a v o i d g r o u n d l o o p p r o b l e m s c o n n e c t s h i e l d t o e...

Страница 22: ...f the STATE 200 unit by removing the 2 screws on each side holding down the cover 3 To remove a module loosen the screw on top of the module on Type B module also unplug the small connector cable gent...

Страница 23: ...OWER ON light turns Green when the system is powered up 4 2 Maintenance 4 2 1 Cleaning Periodically wipe the case with a damp cloth and mild water based detergent Do not use abrasives or solvent Clean...

Страница 24: ...Copyright VibroSystM Inc 2011 24 Using the STATE 200 Unit Rev 0...

Страница 25: ...240 VAC 50 60 Hz If the unit does not receive power verify the source wiring starting with the external circuit breakers protecting the unit If the unit receives power verify the fuses in the fuse hol...

Страница 26: ...essage indicates Signal in range as on the following screen capture If the ZOOM Look service shows the status associated to the STATE 200 unit with the message Acqui sition Unit Not OK one of the foll...

Страница 27: ...DHCP server Select Control Panel Administrative Tools DHCP In the example above only one address is assigned to a STATE 200 unit However in a longer list a combi nation of elements is used for identif...

Страница 28: ...ver use the ZOOM Configuration program to verify the ZOOM configuration Refer to the ZOOM 6 Look Plug in User s Guide 5 2 2 Configuration Troubleshooting In the following cases the STATE 200 unit is c...

Страница 29: ...ZOOM Look service shows the status associated to a sensor the configuration is incorrect for the type of sensor physically connected to the unit To correct the configuration use the ZOOM Configuration...

Страница 30: ...Copyright VibroSystM Inc 2011 30 Troubleshooting the STATE 200 Unit_Rev 0...

Страница 31: ...d 0 to 5 VDC 0 to 5 VDC isolated 5 to 5 VDC 5 to 5 VDC isolated 0 to 10 VDC 10 to 10 VDC 10 to 10 VDC isolated AD9T AD13T AD6 AD6T AD11 AD11T AD7 AD12 AD12T 5 5 6 7 6 7 6 7 6 7 6 7 6 7 6 7 B B A A A A...

Страница 32: ...V output 5 W without modules not providing any 24V output Fuse Two 2 fuses 250V 3 15A slow blow one on Line one on Neutral 6 2 Environmental Characteristics Temperature range Operation 0 to 50 C 32 to...

Отзывы: