Copyright © VibroSystM Inc., 2011
11
STATE-200 General Description_Rev. 0
●
REAR VIEW
Sixteen Analog Input ports are provided to receive signals from various remote sensors. Each port also
features a 24V
DC
power output available to the associated measuring chain.
Permanent wiring is done on 7-position removable mini screw terminals connectors
An Ethernet network interface is provided to allow transmission of data to a ZOOM Controller.
AC-input connection to power supply. A 3 position removable female screw terminal connector allows wiring
of AC power input. The STATE-200 Unit should be installed in compliance with national and local electrical
code.
The unit relies on dual fuse protection. Replace only with same type of fuse: time-delay, 250V, 3.15A, 5x20
mm.
The protective conductor terminal on the rear panel must be connected to a grounding point in compliance
with local regulations. Grounding through the protective conductor terminal is essential for safety purposes
as well as to provide better efficiency against ESD and EMI perturbations.
Analog Input Ports
Ethernet port
Power Input
Protection Fuses (2)
Protective conductor terminal
1
12
4
3
5
1
2
3
4
5
Содержание STATE-200
Страница 2: ...Copyright VibroSystM Inc 2011 2 STATE 200 Installation Manual_Table of Contents Rev 0...
Страница 4: ...Copyright VibroSystM Inc 2011 4 STATE 200 Installation Manual_Table of Contents Rev 0...
Страница 12: ...Copyright VibroSystM Inc 2011 12 STATE 200 General Description_Rev 0...
Страница 24: ...Copyright VibroSystM Inc 2011 24 Using the STATE 200 Unit Rev 0...
Страница 30: ...Copyright VibroSystM Inc 2011 30 Troubleshooting the STATE 200 Unit_Rev 0...