STATE-200 Installation and Field Wiring_Rev. 0
●
3.5.2 Module Installation or Replacement
To replace or add a new module, the STATE-200 must be turned off, all connectors unplugged, and the casing
extracted from the instrument rack and opened.
1. To remove a connector from an input port or the power input
port, loosen the two screws securing the connector to the
socket. If needed, use an extractor tool to pull a cabled
connector off its socket. Do not pull on the wires.
2. Open the casing of the STATE-200 unit by removing the 2
screws on each side holding down the cover.
3. To remove a module:
- loosen the screw on top of the module;
- on Type B module, also unplug the small connector cable;
- gently pull out the module.
Refer to
Table 1: “Input Modules Available,”
on page 31 to see
the type of casing for each model of input module.
4. Insert the new module, tighten the screw on top of the module,
and in the case of a Type B module, also plug the small
connector cable to the connection pins of the corresponding
location.
5. Adjust the DIP-switches configuration according to type of the
module (refer to
"3.5.1 Input wiring and DIP switch setting"
page 18).
6. Place the cover back and reinstall the screws on each side.
Содержание STATE-200
Страница 2: ...Copyright VibroSystM Inc 2011 2 STATE 200 Installation Manual_Table of Contents Rev 0...
Страница 4: ...Copyright VibroSystM Inc 2011 4 STATE 200 Installation Manual_Table of Contents Rev 0...
Страница 12: ...Copyright VibroSystM Inc 2011 12 STATE 200 General Description_Rev 0...
Страница 24: ...Copyright VibroSystM Inc 2011 24 Using the STATE 200 Unit Rev 0...
Страница 30: ...Copyright VibroSystM Inc 2011 30 Troubleshooting the STATE 200 Unit_Rev 0...