NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
76
SM-DU Switch Settings (cont’d from previous page)
DIP Switch S3
Set via
Software
Contactor
Type
Safe Mode
Dry Contact
Description of Status
1
2
3
4
Off
NA
Shunt parameter is set through DIP switch.
On
Shunt parameter is set via software. (Note
1)
NA
Off
NA
Bi-Stable Contactor (Note 1)
On
Mono-Stable Contactor
NA
Off
NA
LVD / reconnection is disabled upon
communication failure.
On
LVD / reconnection is enabled upon
communication failure. (Note 1)
NA
On
LVD2 is a Dry Contact
Off
LVD2 (Note 1)
DIP Switch S3
Shunt 5 Setting
Reserved
Calibration
Mode
Description
of Status
5
6
7
8
Off
Off
NA
Shunt 5 is Disabled (Note 1)
Off
On
Shunt 5 is Used for Battery
On
Off
Shunt 5 is Used for Load
On
On
Set via Software
NA
Off
Operation Mode (Note 1)
On
Calibration Mode
Note 1: Setting for this system.