NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
20
Placing and Securing the Relay Rack(s) to the Floor (if applicable)
System components are factory mounted in a relay rack, on shipping rails, or in an enclosure as specified when
ordered.
Systems Installed in a Relay Rack
The system consists of one to six bays. For busbar-connected systems (List 1 with List 2/List 3), locate relay
racks in a line adjacent to each other, with no space between them. Place the List 1 Main Bay at the right or left
side end, then the List 2 Supplemental Bay, then the List 3 Supplemental Bay (if furnished), etc.
Secure the relay rack to the floor per site requirements. Refer to “General Requirements” on page 16.
Ventilation Requirements
Refer to the “General Requirements” on page 16.
Relay Rack Floor Mounting Dimensions
for relay rack floor mounting dimensions.