122
Figure 58:
400 Volts DC Input and Equipment Grounding Connections to Module Mounting Assembly
588705000 List 42 (1 Feed per 3 Converters)
Holes for 3/4"
Conduit Fitting
(Input)
Rear View
Converter Module Mounting Slots
(front view)
Conv.
1
Conv.
2
Conv.
3
Conv.
4
Conv.
5
Conv.
6
CONVERTER 400 VDC INPUT FEEDS
1 FEED PER 3 CONVERTERS
+
-
+
-
Holes for 3/4"
Conduit Fitting
(Input)
Rear View
FRAME GROUND CONNECTION
ONE 10-32 X 3/4" STUD
AND HARDWARE.
Recommended torque: 23 in-lbs.
FRAME GROUND CONNECTION
ONE 10-32 X 3/4" STUD
AND HARDWARE.
Recommended torque: 23 in-lbs.
400 VDC IN
Feed 2
(Converter
Modules
4-6)
400 VDC IN
Feed 1
(Converter
Modules
1-3)
Wire Size Capacity: 6-14 AWG.
Recommended Torque: 18 in-lbs.