NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
168
Load Connections to Dual Voltage Distribution Panels
Figure 85:
List DA: -48V/+24V Distribution Panel, (17) –48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions
(with Return Busbar) and (4) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar)
Figure 86:
List DB: -48V/+24V Distribution Panel, (13) –48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions
(with Return Busbar) and (8) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return
Busbar)
Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
-48V Distrib
ution
+24V
Distribution
Observe proper
polarity when making
load connections.
WARNING!
Caution: A 100 A circuit breakers and fuses can be used without a space
provided the continuous operating current in each 100 A device does not exceed
64 A. A 175 A or greater circuit breaker shall have an empty mounting position
between it and any other overcurrent protective device.
Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
-48V Distrib
ution
+24V Distrib
ution
Observe proper
polarity when making
load connections.
WARNING!
Caution: 100 A circuit breakers and fuses can be used without a space provided
the continuous operating current in each 100 A device does not exceed 64 A.
A 175 A or greater circuit breaker shall have an empty mounting position between it
and any other overcurrent protective device.