![Vertiv NetSure
7100 Series Скачать руководство пользователя страница 155](http://html.mh-extra.com/html/vertiv/netsure-7100-series/netsure-7100-series_installation-manual_1007935155.webp)
Vertiv
|
NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
155
Control Bus Connections between Controller and Module Mounting Assemblies Spec. No.
588705300
Each Spec. No. 588705300 module mounting assembly in the system is daisy-chained to the controller.
Controller CAN Bus connectors are located at the left and right rear of each shelf. These connectors are used
to interconnect the shelves to the controller and to other shelves. The right side connector is factory jumpered
so both connectors can be accessed from the left side of the shelf. Refer to
and an interconnect diagram. These connections are factory made for shelves factory installed. The
connection must be made if a rectifier field expansion shelf is installed as shown in
. For field
expansion, refer to the procedure in Power System User Instructions UM582127000.