Direct AC Input Connections to 588705400 List 04 Module Mounting Assemblies
Spec. No. 588705400 List 04 is equipped with plug-in AC input connectors located on the rear of the shelf. AC
input line cords with mating connectors are available (see SAG582127000). Make AC input connections per
Figure 53:
Nominal 277 VAC / 480 VAC Input Connections (Three-Phase) to a 588705400 List 04 Module
Mounting Assembly
RectifierA
C input
conne
ctions ar
e made u
sing
the supp
lied AC input
line cords
connected
here.
Rear
M4 Frame
Ground Screw
M4 Frame
Ground Screw
Rectifiers are numbered left to
right as viewed from the front.
AC Input for
Rectifier Positions
#1, #2, #3
Rear
AC Input for
Rectifier Positions
#4, #5, #6
White*
Black*
Red*
Orange*
Green*
N
L1
L2
L3
Ground
* Color of Input Line Cord Lead
Module Input Connector
(Cabinet Rear View)
AC Input
Line Cords
P/N 562045
P/N 562045
Plug End
Rectifier AC Input
(277 VAC / 480 VAC, Three Phase, 20 A)
Terminal G
(Green Wire)
Terminal Z
(Orange Wire)
Terminal Y
(Red Wire)
Terminal X
(Black Wire)
Terminal W
(White Wire)
Input Connections are
Made using the Ordered