a)
Requirement:
SCU+ “Major/Minor” alarm indicator goes from red to off.
b)
Requirement:
Press ESC repeatedly to return to the Main screen. SCU+ displays “Normal”.
c)
Requirement:
All external alarms deactivate.
Final Steps
1.
Verify the Distribution Unit door is closed and secured.
2.
Verify all Rectifier Modules and the Controller are fully seated, latched, and the latch handle screws
secured.
3.
Verify there are no external alarms, and the local indicators are as shown in