Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
21
Installing Circuit Breakers and Fuses
GMT Load Distribution Fuses (List BF and NF)
Procedure
NOTE!
1.
Open the Distribution Unit’s front access panel.
2.
Install correctly sized GMT fuses into the fuse holders located inside the Distribution Unit, as required. If
a dummy fuse is installed, first remove the dummy fuse. Install a safety fuse cover over each GMT fuse.
3.
When finished, close the Distribution Unit’s front access panel.
Figure 6:
Installing GMT Load Distribution Fuses (List BF and NF)
Front
GMT Fuse
Positions
(Max. 15A)
GMT Fuse
Positions
(Max. 10A)
Front access panel
removed in illustration
for clarity.