Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
16
Securing the Power/Distribution Shelf to a Relay Rack or Cabinet
The shelf is designed to mount in a standard 19” or 23” wide relay rack or cabinet frame having 1” or 1-3/4”
multiple drillings. Refer to SAG582136700 for overall dimensions and a list of available relay racks.
NOTE!
Refer to the General Requirements section at the beginning of this section for Ventilation
Requirements.
NOTE!
Multiple Power/Distribution Shelves may be stacked one above the other with no space between
the shelves.
Mounting the Shelf
1.
Secure shelf mounting angles to relay rack or cabinet at two (2) locations per side. Use grounding
washers at one (1) location per side. Proper orientation of grounding washers enables teeth to dig into
paint for a secure ground connection. Torque connections to 70 in-lbs.
NOTE!
Compliance with Telcordia GR-1089-CORE requires that prior to mounting the
Power/Distribution Shelf to the equipment rack:
•
All paint must be removed from the front surface of each equipment rack rail where it mates with a
shelf-mounting bracket, so that good metal-to-metal contact can be established between the shelf
and rack.
•
The shelf-to-rack mating surfaces must be cleaned.
•
Electrical anti-oxidizing compound must be applied to the shelf-to-rack mating surfaces.
Securing the Power/Distribution Shelf to a Wall with a Part No. 553203 Kit
An optional Wall Mount Bracket Kit (Part No. 553203) is available for vertical wall mounting of any List 2 or 6
Power/Distribution Shelf.
NOTE!
Refer to the General Requirements section at the beginning of this section for Ventilation
Requirements.
Procedure
1.
when performing this procedure.
2.
The installer must provide fasteners for securing the shelf to a wall or other vertical surface. Ensure that
the wall and fastening technique are suitable for supporting the weight of the shelf and rectifiers.
Suggested anchors are listed in the illustrations. Refer to System Application Guide SAG582136700 for
shelf weight and additional dimensions.
3.
Attach the brackets to the shelf mounting angles using kit-furnished screws. Torque to 60 in-lbs.
4.
Use drill guide dimensions in the illustration to prepare the wall for customer-furnished fasteners.
Secure the shelf assembly to the wall.
Содержание NetSure 502NGFB Series
Страница 10: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 10 This page is intentionally blank ...
Страница 37: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 37 Figure 14 Controller RJ 45 Ethernet Port ...
Страница 45: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 45 Figure 20 Battery Connections ...
Страница 85: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 85 This page is intentionally blank ...
Страница 86: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA Section 6009 RZ 2020 ...