VCFDVI31 Gas Fireplace Insert

NOte ReGARDING VeNteD pRODuCts

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOte ReGARDING VeNt FRee pRODuCts

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

CARBON MONOxIDe DeteCtOR RequIReMeNts

(2) Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  For  all  side  wall  horizontally  vented  gas  fueled  equipment 

installed in every dwelling, building or structure used in whole 

or  in  part  for  residential  purposes,  including  those  owned  or 

operated by the Commonwealth and where the side wall exhaust 

vent termination is less than seven (7) feet above finished grade 

in the area of the venting, including but not limited to decks and 

porches, the following requirements shall be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — please read and follow these special requirements

2. 

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide  detector  as  required  in  accordance  with  the  above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.
3. 

signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas equipment Venting 

system  provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the  equipment,  the  instructions  provided  by  the  manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas equipment Venting 

system  Not  provided. 

When  the  manufacturer  of  a  Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
2. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions,  all  parts  lists  for  venting  instructions,  and/or  all 

venting design

Содержание VCFDVI31

Страница 1: ...lt a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by loca...

Страница 2: ...Installation Items Needed 19 Check Gas Pressure 21 Gas Shutoff Tool 21 Electrical Installation 22 Electrical Wiring 22 Log Placement 23 Operating Instructions 26 For Your Safety Read Before Lighting...

Страница 3: ...d by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with h...

Страница 4: ...pliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER TESTED TO...

Страница 5: ...tings are shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installation must be in accord...

Страница 6: ...lace Insert 2256QE 560 mm 115 6QE 303 mm 1056 257 mm 2 6QE 56 mm 55 6QE 144 mm 1656 410 mm 24 6QE 621 mm 2756 689 mm 256M 57 mm 2156QE 535 mm 4164 ICFDV insert dims insert dimensions Figure 2 VCFDVI31...

Страница 7: ...cific installation requirements IMPORTANT Your direct vent insert was designed to be installed in an existing wood burning fireplace The location and clearances are subject to local building codes INS...

Страница 8: ...m from the fireplace opening local codes may require a larger hearth The hearth must also extend to both sides of the face FP2959 Figure 3 Mantel Clearances NOTE Side clearance to combustibles is 10 2...

Страница 9: ...DIMS 22 6 568 mm 20 6M 527 mm 16 6M 426 mm 30 6M 781 mm 29N m 759 mm with control box and bracket removed REMOVE COMMAND CENTER BRACKET In order to fit insert into a smaller opening the command center...

Страница 10: ...s well ventilated OPEN ALL WINDOWS DURING INITIAL BURN OFF CURING PHASE Burn your insert for at least six 6 hours on HIGH the first time you use it Place the fan in the OFF position during this time P...

Страница 11: ...g installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious injury property d...

Страница 12: ...resize orifice for use at high altitude contact your dealer High Temp Silicone FP2948 exhaust pipe 3 and 3 UL 1777 Gas Liner Apply high temperature silicone to lines on both ends and secure with two 2...

Страница 13: ...ommended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Fire box Figure 11 Inlet and Exhaust Reline NOTE You may use either reline configuration w...

Страница 14: ...replace screw 3 Use the large end of the tool to unlatch the two 2 glass frame latches 4 Pull glass frame away from unit and lift up and away WARNING HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTI...

Страница 15: ...nnecting six pin connector Set aside Figure 14 FP2969 6pin connector Six Pin Connector FP2969 Figure 14 Disconnect Command Center Cable 4 Carefully insert engine in large opening on inside of firebox...

Страница 16: ...e corner of insert Insert plug end of electric cord through hole in insert and through plastic grommet Slide grommet down electrical cord and reinstall Figure 19 FP2974 grommet Plastic Grommet FP2974...

Страница 17: ...1 front brick retainer bracket on each side with the screws removed in Step 2 4 Carefully set rear brick panel with notch up on log sup port 5 Carefully place right or left side brick panel in place...

Страница 18: ...screws Align slots in baffle plates so the slots are closed Retighten screws NOTE For propane LP units the baffle assembly is com pletely removed for venting under 20 ft 6 m For venting 20 ft and abov...

Страница 19: ...u must reduce incoming gas pressure to between 11 and 13 inches of wa ter If you do not reduce incoming gas pressure burner system regulator damage could occur Install external regulator with the vent...

Страница 20: ...aminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly NOTE The gas line connection...

Страница 21: ...and soap solution or a gas sniffer 4 To check gas pressures at valve turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Turn unit to high Figur...

Страница 22: ...rical supply Electricity is only needed to operate blower Verify proper operation after servicing Electrical connections should only be performed by a qualified licensed electrician Main power must be...

Страница 23: ...nts such as pine cones or vermiculite to the heater Only use the logs supplied with the unit Failure to position the parts in accordance with diagrams below or to use only parts specifically approved...

Страница 24: ...n the right grate tine by placing the notch on the bottom of the log on the rear portion of the grate tine Figure 33 Log 3 LG1125 Figure 34 Log 4 LG1126 Figure 35 5 Install log 3 onto log 2 by placing...

Страница 25: ...h on the bottom of the right side onto the middle or remaining rectangular protrusion on log 2 Figure 36 LG1128 CFDVI log 6 7 Log 6 LG1128 Figure 37 Log 7 8 Install log 6 by placing rectangular notch...

Страница 26: ...Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not func ti...

Страница 27: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will lig...

Страница 28: ...brick panels 2 Remove log support bracket by removing two 2 screws in rear and one 1 screw on each side wall 3 Remove four 4 screws holding burner in place and slide burner to the left and up and out...

Страница 29: ...The slide adjustable air shutter has a range of 1 Figure 40 To increase air mixture open the slide adjustment by gently pulling on the lever When lever stops it has reached its maximum adjustment This...

Страница 30: ...battery Indication for Transmitter X Child Proof Lock out X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Mod...

Страница 31: ...ess button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 41 for location 2 After the RF receiver is on holding the OFF button on the Comman...

Страница 32: ...um Low then Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off...

Страница 33: ...ows The blue LED backlight lights up for 8 seconds when any of the touch buttons is pressed The menus include TIMER THERMO LIGHT FAN and AUX Rear Burner Control The adjustment arrows include ON up and...

Страница 34: ...mmand Cen ter will flash for 10 seconds 4 During the 10 sec onds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a success ful learning Figure 46 TOUCH SCRE...

Страница 35: ...lace will be shut down completely when the timer counts down to zero 6 To exit Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero...

Страница 36: ...down button to increase de crease the blower speed 3 Press the fan button again to confirm the speed set ting If the fireplace is on the blower speed will take effect right away if the fireplace is o...

Страница 37: ...A touch any place in the touch area to bring up the icons then press TIMER but ton and THERMO button at the same time for 3 sec onds The backlight will flash once to indicate that the setting has cha...

Страница 38: ...is blank 2 Check battery installation or replace batteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The transmitte...

Страница 39: ...t and lint to the surface of the glass The initial paint curing of the appliance can also leave a slight film on the glass This is a temporary problem You should clean the glass after the first two we...

Страница 40: ...main burner and pilot 5 Carefully replace log set and embers in their correct positions Refer to Pages 23 through 25 6 Replace door 7 Relight pilot Refer to Page 27 8 Turn on main burners Allow logs t...

Страница 41: ...is found heater must be adjusted Contact dealer where you bought heater 4 Remove rock wool Clean burner and burner ports Figure 59 5 Replace log set and rock wool according to instructions on Pages 23...

Страница 42: ...ugh Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check...

Страница 43: ...20304166 VCFDVI31 Gas Fireplace Insert 43 REPLACEMENT PARTS 24 6 1 2 3 4 5 8 11 12 14 16 39 32 34 33 38 4166 VCFDVI31 parts 10 17 27 25 26 31 30 29 7 9 13 15 18 19 20 21 22 11 19 23 40...

Страница 44: ...Flex Line w Mounting Plate 1 20303795 20303795 25 Control Board NG SCS 1 80D0018 80D0018 26 Command Center SCS 1 80D0005 80D0005 27 AC Module SCS 1 80D0004 80D0004 28 Remote Control 1 TSFSC TSFSC 29...

Страница 45: ...5b Glass Frame Textured Mocha ICF30GTTM 6a Rectangular Double Door Satin Black ICF30R2DSB 6b Rectangular Double Door Vintage Iron ICF30R2DVI 6c Rectangular Double Door Textured Mocha ICF30R2DTM 7a Arc...

Страница 46: ...ly with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please r...

Страница 47: ...d if the appliance is not installed by a qualified installer in accor dance with the installation instructions The limited 10 year warranty will also be void if the appliance is not operated and maint...

Страница 48: ...s Fireplace Insert MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com Efficiency Ratings Model EnerGuide Ratings D O E Fireplace Efficiency AFUE VCFDVI31LENTSC 69 0 68 0 VCFDVI31LENTSC 72 9 70...

Отзывы: