Installation Guide

Power Monitoring

H81xx

TM

10. H8163 and H8167:

  Set the Pulse Rate selection switch to the desired output rate (kWh per pulse). Note that 0.1 is not valid for 

1600 A systems, and 0.1 and 0.25 are not valid for 2400 A systems.

N

A

+ A D + B D

+ C D

B

C

N

A B

C

+ - + - + -

Display

Plain

Full

Black

Black

Yellow

Yellow

Red

Red

1.0

0.5

0.25

0.1

11. Secure the meter cover shut using a padlock, wire tie, or other locking device.

12. Apply power to the meter.

13. Check the display. At initial power-up, the meter checks each phase. If the phasing is correct, an OKAY message appears. If 

the phasing is incorrect, an error message indicates which color leads are not connected properly. Disconnect power before 
reconnecting leads.

14. Check the power reading. Expected power is estimated as follows:

kW = Volts(L-L) * Amps * 1.732 * PF 1000

kW = horsepower * 0.746

15. To reset the kWh accumulator to zero, press and hold the two pushbuttons on the inside of the meter cover for 10 seconds.

16. To reset the kW max. register, press and hold the two pushbuttons on the inside of the meter cover for 5 seconds.

Installation (cont.)

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...