Installation Guide

Power Monitoring

H81xx

TM

5.  Use color coding to attach current transformer (CT) leads to the input terminals (e.g. red labeled lead to red terminal). Polarity 

is indicated in the wiring diagrams, but the meter is not polarity sensitive. See the Wiring section.

6.  Use color coding to connect voltage leads to phase conductors (e.g. red transformer lead to red terminal). The meter is powered 

from the monitored source, so connect the voltage leads to a circuit that is normally left on. See the Wiring section.

7.  H8163 and H8167:

  Connect the output terminals to the control/data acquisition system. The Pulse Output is normally open. For 

the H8163, the Phase Loss Output is normally open, and for the H8167, it is normally closed. Both are rated for 24 VAC/VDC@100 

mA maximum. Ensure that the installation method and insulation ratings conform to local and national electrical codes.

N

A

+ A D + B D

+ C D

B

C

N

A B

C

+ - + - + -

Display

Plain

Full

Black

Black

Yellow

Yellow

Red

Red

Pulse Output 

Terminal

Phase Loss 

Output 

Terminal

8.  Set the backlight enabling jumper as desired. Remove the jumper to disable the backlight.

Backlight Enable Jumper

9.  Set the Display Data jumper for either Plain or Full settings. Plain mode cycles the display through five data elements (kW, max. 

kW since last reset, average PF, line-to-line voltage, and amps) for four seconds each. Full mode cycles through all of the data 

available in the meter. See the Information Reporting section for more details.

20 seconds per cycle 

90 seconds per cycle 

kW

max. kW

PF

Volts L-L

Amps

kW

max. kW

PF

Volts  L-L

Amps

kVAR

kW  Phase  A

kW  Phase  B

kW  Phase  C

PF  Phase  A

etc.

Installation (cont.)

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...

Отзывы: